6.1.7 DC wiring for single MPPT operation
Nr.
OK
NOK Check
35.
❑
❑
The inputs of the power units are outside of the inverter wired in parallel with the DC
busbars.
36.
❑
❑
The DC feed lines between the DC busbars and the inputs of the inverter have been fused.
37.
❑
❑
The DC busbars have been dimensioned and fused for the maximum possible current
specified in the installation manual (see 5.7 Application examples).
38.
❑
❑
The DC feed lines between the PV module or MaxConnect and the DC busbars are fitted
with fuses. These have been fitted both on the plus pole and the minus pole.
39.
❑
❑
The DC feed lines between the PV modules or between MaxConnect and the DC busbars
are dimensioned for the maximum possible current.
6.1.8 AC wiring
Nr.
OK
NOK Check
40.
❑
❑
The measurement of the AC voltage prior to commissioning the station revealed the follow-
ing values: SM330TS-SV: 270 V … 285 V / SM360TS-SV: 310 V … 330 V.
41.
❑
❑
The AC overvoltage protection conforms with the requirements of overvoltage category 2.
42.
❑
❑
The line cross section for the AC connection in the inverter is no less than
3 x 95 mm
2
per phase.
43.
❑
❑
The AC feed lines in the inverter have been correctly connected (mains phases are
clockwise). The tightening torque of the 9 nuts is in conformance with the specs in the
installation manual.
44.
❑
❑
The delivered phase separation elements have been fitted between the lugs inside the
inverter.
45.
❑
❑
Each inverter can be disconnected separately by an AC circuit breaker or an 800A NH fuse
switch disconnector on the AC side.
46.
❑
❑
The autonomous power supply transformer is fused on the primary and secondary sides.
6.1.9 Data communication
Nr.
OK
NOK Check
47.
❑
❑
The modular bus connection between the MCU and the closest inverter is realised with the
Cat. 6 S/FTP communications cable included in the delivery (5m cable).
48.
❑
❑
The modular bus connections between the inverters are realised with the Cat. 6 S/FTP
communications cables included in the delivery (2 m and 10 m cable).
49.
❑
❑
The terminal plug for the modular bus is plugged into the final power unit.
50.
❑
❑
Each of the power units has a unique modular bus address. The addresses have been
assigned in conformance with the instructions in the installation manual.
6.1.10 Earthing
Nr.
OK
NOK Check
51.
❑
❑
All the earth connections have been check with the ohmmeter.
52.
❑
❑
The inverter is earthed with two 95 mm
2
earthing cables.
53.
❑
❑
The MCU is earthed to the station with a 10 mm
2
earthing cable.
54.
❑
❑
The star point of the 400 V-coil of the transformer for the station's own power supply is
earthed.
55.
❑
❑
The AC-side overvoltage protection of the inverter is earthed.
56.
❑
❑
the DC fuse box is earthed with a 10 mm
2
earthing cable to the station.