to comply. The SOLARWATT pricelist contains 
matching cablesets, plugs, cables and installati

-

on accessories. When connecting the modules, 
ensure that the plugs engage with an audible 

click.  The  common  bending  radii  of  at  least  5 

times the outer cable diameter must be com

-

plied with. It is recommended to lay the cable 

firmly so that they are not subjected to mecha-

nical loads. The cable and connector must not 
exposed to moisture and will not rest on the 

ground or floor. 

Solar modules generate electrical energy on the front side during incidence of light. A 

system with multiple solar modules can generate life-threatening voltages and electri-
cal currents. Do not touch the electrical connections or cable ends while the solar mo-

dule is exposed to light.

WARNING

To ensure safety and compliance with the 
technical data of the products, only original 
tools of the manufacturer may be used in the 

self-assembly of solar cables.
Connection of modules in series is only permit-

ted up to the maximum system voltage as listed 
in applicable data sheet. The maximum num

-

ber of solar modules installed parallel without 
string fuse is two. Please comply with the value 

specified in the data sheet for reverse current 

feed and only use standardized photovoltaic 

cables (recommendation: at least 4 mm² cable 
cross-section).  The modules must not be allo-

wed to operate on a short circuit permanently. 
The solar modules correspond to application 
class II and can therefore be operated in sys

-

tems  with  dangerous  DC  voltages  (larger  than 
120 VDC in accordance with IEC 61730). Solar 

modules in this application class can be used in 
systems with unrestricted access, the relevant 
regulations must be complied with. SOLARWATT 

solar modules qualified within this application 
class  in  accordance  with  IEC  61730  fulfill  the 

requirements of protection rating II with correct 
electrical installation.

Under  normal  installation  conditions,  a  solar 
module  can  deliver  a  higher  current  and/or 

higher voltage than under standardized test 

conditions. Consequently, the specified values 
on the solar module for short circuit current ISC 
should be multiplied by 1.25 and the open cir-
cuit voltage UOC should be multiplied by a fac-
tor of up to 1.25, based on the lowest expected 

ambient temperature for the given installation 
location, to determine the rated voltage values 
of components, the rated current values of con

-

ductors, the size of fuses and for dimensioning 
control units connected to the solar modules.
Any type of soiling on the plug contacts befo

-

re or after installation (dust, moisture, aerosols 

containing salt, etc.) has a negative influence on 

the system function over the intended service 
period. For this reason it is necessary to pay 
particular attention to cleanliness during ins

-

tallation. The use of lubricants is not permitted. 
Always protect unplugged connectors against 
soiling of any type during transport, storage, 
and during installation, as the connectors only 
satisfy the requirements for their protection ca

-

tegory when plugged in. It is forbidden to open 
the junction box or modify or remove the cable.  
The cables must be laid so that mechanical 
strain on the conductors and connections is ru

-

led out. Take into account the product-specific 
length of the connection cable specified in the 

PAGE 6 | SUBJECT TO CHANGE | © 2019 SOLARWATT GMBH | AZ-TM-PMS-1703 | REV 006 | STATUS: 08/2019

Summary of Contents for VISION 36M GLASS

Page 1: ...tion EN 62446 Grid coupled photovoltaic systems IEC 60364 Erection of low voltage systems VDE DIRECTIVES VDE 0100 Erection of low voltage systems VDE 0105 100 Operation of electrical systems EXCLUSION...

Page 2: ...rements please contact the responsible local authorities and the network operator SOLARWATT solar modules are made from high quality materials and high performance solar cells and are therefore extrem...

Page 3: ...ixed to suitable substructures which are designed for the relevant mechanical wind and snow loads as well as the weight of the solar modules The instructions from the installation system manu facturer...

Page 4: ...for the calculation of the snow loads on the module It is important to note that these standards are designed for impact on structures and do not explicitly take into account the ins tallation of sol...

Page 5: ...ctor of 1 5 in accordance with the IEC 61215 standard and apply to flat and sloping roofs with unobstructed snow slipping The maximum given load is valid only for on roof application Fixing by long si...

Page 6: ...pplication class can be used in systems with unrestricted access the relevant regulations must be complied with SOLARWATT solar modules qualified within this application class in accordance with IEC 6...

Page 7: ...ay also be used in the recommended dose Do not use aggressive cleaning agents or metal objects as they can be particularly dama ging to the hardened glass surface The electric cables should where acce...

Page 8: ...ite the high quality of our products please contact your dealer directly or SOLARWATT GmbH Maria Reiche Str 2a 01109 Dresden Germany Tel 49 351 8895 0 Fax 49 351 8895 100 info solarwatt com Certified...

Reviews: