DANGER!

Electric shock

The connection of two or more modules in series results in the accumulation of 

voltage and imposes danger. Do not insert electrically conductive parts into con-

nectors! Do not attach solar modules and wiring with wet connectors! Make sure 

to work with dry tools and under dry working conditions!

Work on live parts

When  working  on  wiring,  use  and  wear  protective  equipment  (insulated  tools, 

insulated gloves, etc.)!

ATTENTION

Do not use damaged modules. Do not dismantle modules. Do not remove any parts 

or nameplates fitted by the manufacturer. Do not apply paint or adhesives to the 

module, nor work on it with sharp objects.

WARNING!

Arcing

Modules  generate  direct  current  (DC)  when  exposed  to  light.  When  breaking  a 

closed circuit, a dangerous arc may be generated. Do not cut any live wires. 

Safe installation

Do not carry out installation work in strong winds. Secure yourself and other per-

sons against falling. Secure work materials against dropping. Ensure a safe working 

environment so as to prevent accidents. 

Fire protection/explosion protection

Modules must not be installed in the vicinity of highly flammable gases, vapors or 

dusts (e.g. filling stations, gas tanks, paint spraying equipment). The safety instruc-

tions for other system components must also be followed. Make sure to comply 

with  local  standards,  building  regulations  and  accident  prevention  regulations 

during installation. For roof installation, modules must be mounted on a fire-resi-

stant base material. 

Unpacking and intermediate storage

Do not use the junction box as a handle. Do not place modules roughly on hard floor or 

on their corners. Do not place modules on top of each other. Do not step or stand on 

modules. Do not place any objects on modules. Store modules in a dry place. 

Grounding of module and frame

We recommend ensuring the functional grounding of the module metal frame. If an 

exterior lightning protection system is already provided, the PV system has to be inte-

grated into the protection concept against direct lightning stroke. Local standards shall 

be observed.

Grounding in the US and Canada

Suitable ambient conditions

Artificially  concentrated  sunlight  shall  not  be  directed  on  the  module  or  panel.  The 

module must neither be immersed in water nor be exposed to continuous wetting (e.g. 

by fountains). Exposure to salt or sulfur (sulfur sources, volcanoes) implies a risk of cor-

rosion. The module must not be used for maritime (e.g. boats) or automotive (vehicles) 

purposes. The module must not be exposed to extraordinary chemical loads (e.g. emis-

sions from manufacturing plants). If the modules are installed on stables, a distance of 

3.28 ft (1 m) to ventilation openings shall be ensured; apart from this, the modules shall 

not be used as a direct roof panel on stables.

Appropriate installation situation

Make sure that the module meets the technical requirements of the overall system. 

Other system components should not exert any adverse mechanical or electrical influ-

ences on the module. Modules may bend under high loads. For this reason, sharp-edged 

fixing elements or other sharp objects (e.g. cable ties on mounting sections) must not 

be mounted near the module back side. For modules connected in series, only modu-

les  of  the  same  amperage  rating  may  be  used  together.  For  modules  connected  in  

parallel, modules with the same voltage ranges must be used together. The modules 

must  not  be  operated  at  a  higher  voltage  than  the  permissible  system  voltage.  The 

inside opening of the frame corner element is intended for water drainage and must 

not be blocked. For system documentation, please note the serial numbers.

Optimum installation

In  order  to  avoid  performance  losses,  all  modules  connected  in  series  should  be 

arranged with the same orientation and tilt angle. The modules should be installed in 

an all-season shadow-free area. Even partial shadowing results in yield losses and is to 

be avoided. Ventilation of the module back side will prevent heat build-up adversely 

Mounting

The  modules  must  be  securely  fixed  at  a  minimum  of  4  locations  on 

the  substructure.  Fixing  is  only  allowed  in  designated  areas.  In  regards 

to  “Top-Down”  mounting  methods,  the  minimum  clamping  pressure  is  

50 N/mm² (72.5 psi). Do not drill any holes into the module. Use corrosion-proof fixing 

material.

Electrical connection

The modules are provided with factory-assembled cables and connectors . Do not open 

the junction box in any case. Connectors may only be connected under dry conditions. 

Make sure to avoid gaps in a plugged connection. Only singlecore solar cables with an 

adequate  cross-section  (4  mm²  minimum)  and  appropriate  connectors  may  be  used 

for connecting the modules. Cables should be attached to the installation system by 

means of UV-resistant cable ties. Exposed cables should be protected against sunlight 

and damage by suitable precautions (e.g. conduits) In order to limit voltages released by 

indirect lightning shock, the area of all conductor loops must be reduced to a minimum. 

Check that wiring is correct (polarity!) prior to starting the generator. 

Cleaning

cleaning by rain). In case of heavy soiling, it is recommended to clean the modules with 

plenty of water (tap water or deionized water) without any cleaning agents.  If necessa-

ry, a soft cleaning device (sponge.g. soft brush with split bristles) maybe be used. In case 

of soiling by dust or sand the modules can be cleaned with a soft brush without using 

Maintenance

We recommend regular inspections of the system to ensure that:

1.  All fixtures are securely tightened and corrosion-free;

2. Wiring is securely connected, properly arranged and free of corrosion;

3. Cables are free of damage;

Please also observe applicable standards. 

Disclaimer of liability

SolarWorld  AG  does  not  guarantee  the  operational  capability  and  functionality  of 

modules if the instructions contained in the present user information are not complied 

with.  Since  compliance  with  these  instructions  and  the  conditions  and  methods  of 

installation, operation, use and maintenance of the modules are not checked or moni-

tored by SolarWorld AG, SolarWorld AG accepts no liability for damage arising through 

improper use or incorrect installation, operation, use or maintenance. Furthermore, lia-

bility for infringements of patent law or of other third party rights arising from the use 

of the modules is excluded unless we are automatically liable by law.

EN

Table: Recommended components for grounding in the US and Canada

Item

Manufacturer/Description

Tightening torque

Lay-In lug  1

Ilsco GBL-4DBT (E34440)

Type F Thread Cutting Screw  SS #10-32

32 Ibf-in (3.6 Nm)

Bolt 

#10-32, SS

25 lbf-in (2.9 Nm)

Serrated washer 

M5, SS  

Washer 

ID 9/64’’, OD 3/8’’, SS 

Nut 

#10-32, SS 

2

3

4

5

6

Underwriters Laboratories Information (U.S. and Canada)

The fire rating of this module is valid only when mounted in the manner specified in 

the mechanical mounting instructions. The module is considered to be in compliance 

with UL 1703 only when the module is mounted in the manner specified by the moun-

ting instructions below. A module with exposed conductive parts is considered to be 

in compliance with UL 1703 only when it is electrically grounded in accordance with 

the instructions presented below and the requirements of the National Electrical Code. 

Where  common  grounding  hardware  (nuts,  bolts,  star  washers,  spilt-ring  lock  was-

hers, flat washers and the like) is used to attach a listed grounding/bonding device, the 

attachment must be made in conformance with the grounding device manufacturer’s 

instructions. Common hardware items such as nuts, bolts, star washers, lock washers 

and the like have not been evaluated for electrical conductivity or for use as grounding 

devices and should be used only for maintaining mechanical connections and holding 

electrical grounding devices in the proper position for electrical conductivity. Such devi-

ces, where supplied with the module and evaluated through the requirements in UL 

1703, may be used for grounding connections in accordance with the instructions provi-

ded with the module. The electrical characteristics are within ±10 percent of the indica-

ted values of ISC, VOC, and Pmax under standard test conditions (irradiance of 100 mW/

cm², AM 1.5 spectrum, and a cell temperature of 25°C (77°F)). Under normal conditions, a 

photovoltaic module is likely to experience conditions that produce more current and/

or voltage than reported at standard test conditions. The requirements of the Natio-

nal Electrical Code (NEC) in Article 690-8 shall be followed to address these increased 

outputs. To reduce the operating temperature the module has to be mounted on any 

surface with a minimum distance of 4 inches (10 cm). In Canada the installation shall 

be in accordance with CSA C22.1, Safety Standard for Electrical Installations, Canadian 

Electrical Code, Part 1.

B)

A)

1

2

1

3

4

5

6

General Information

This module is rated for use in application class A according to IEC 61730. For the elec-

trical ratings please refer to the datasheet. Under normal conditions, a photovoltaic 

module  is  likely  to  experience  conditions  that  produce  more  current  and/or  voltage 

than reported at standard test conditions. Accordingly, the values of ISC and VOC mar-

ked on this module should be multiplied by a factor of 1.25 when determining compo-

nent voltage ratings, conuctor current ratings, fuse sizes, and size of controls connected 

to the PV output.“

The modules can be connected at the module corner (A) or at the holes provided in the 

flange (B) using a lay-in lug. The lug must be a tin-coated copper lug, silver in color. Do NOT 

use a bare copper lug, which is brown. Any grounding method and components listed 

according to NEC requirements are also acceptable in the US and Canada. 