DANGeR!

electric shock

The connection of several modules in series creates increased voltage and may 

impose danger. Do not insert electrically conducting parts into connectors! Do 

not install  solar modules and wiring with wet connectors! Make sure to work 

with dry tools and under dry working conditions!

Work on live parts

When working on wiring, use and wear protective equipment (insulated tools, 

insulated gloves, etc.)!

ATTeNTION

Do not use damaged modules. Do not dismantle modules. Do not remove any 

parts or nameplates installed by the manufacturer. Do not apply paint or adhe-

sives on the back side. Do not work on modules with sharp objects.

WARNING!

Arcing

Modules generate direct current (DC) when exposed to light. When breaking a 

closed circuit, a dangerous arc may be generated. Do not cut any live wires. 

Safe installation

Do not carry out installation work in strong winds. Secure yourself and other 

persons to prevent falls. Secure work materials against dropping. Ensure a safe 

working environment so as to prevent accidents. 

fire prevention/explosion prevention

Modules must not be installed in the vicinity of highly flammable gases, vapors 

or dusts (e.g. filling stations, gas tanks, paint spraying equipment). The safety 

instructions for other system components must also be followed. Make sure to 

comply with local standards, building regulations and accident prevention regu-

lations during installation. For roof installation, modules must be mounted on a 

fire-resistant base material. 

Unpacking and intermediate storage

Do not use the junction box as a handle. Do not place modules roughly on hard sur-

faces or on their corners. Do not place modules on top of each other. Do not step or 

stand on modules. Do not place any objects on modules. Do not work on modules 

with sharp objects. Store modules in a dry place. Leave modules in original packaging 

until ready to install.

EN

Table: Recommended components for grounding in the US and Canada

Item

Manufacturer/Description

Tightening torque

Bolt (1)

#10-32, SS

25 Ibf-in (2.9 Nm)

Serrated washer (2)

M5, SS

Washer (3)

ID 9/64’’, OD 3/8’’, SS

Nut (4)

#10-32, SS

Lay-In lug (5)

Ilsco GBL-4DBT (E34440)

35 in-lb, 4-6 AWG stranded

25 in-lb, 8 AWG stranded

20 in-lb, 10-14 AWG sol/str

Body Conductor 

Diameter

Voltage Diode

Max. Series Fuse

IEC

12-14 AWG (2.5 - 4 mm²) 5.5 - 7.8 mm

1000 V

DC

SL1011

15 A

UL

12 AWG (4 mm²)

7.1 ± 0.2 mm

600 V

DC

SL1011

15 A

General Information

This module is rated for use in application class A according to IEC 61730. For the elec-

trical ratings please refer to the datasheet. Under normal conditions, a photovoltaic 

module is likely to experience conditions that produce more current and/or voltage 

than reported at standard test conditions. Accordingly, the values of ISC and VOC 

marked on this module should be multiplied by a factor of 1,25 when determining 

component voltage ratings, conuctor current ratings, fuse sizes, and size of controls 

connected to the PV output.“

Assembly

Recommended angle of inclination for photovoltaic operated stand-alone 

systems/year-round use.

Latitude

fixed angle of inclination

0° - 15°

15°

15° - 25°

equal to the latitude

25° - 30°

La 5°

30° - 35°

La 10°

35° - 40°

La 15°

over 40°

La 20°

Your local photovoltaic dealer can give you information about a suitable installa-

tion location and method.

Grounding of the module and frame

We recommend ensuring the functional grounding of the module metal frame. If 

an exterior lightning protection system is already provided, the PV system has to be 

integrated into the protection system against direct lightning stroke. Local standards 

shall be observed.

Grounding in the US and Canada

Grounding hardware can be installed utilizing a lay-in lug, bolt with serrated washer, 

washer and nut. 

The lug must be a tin-coated copper lug, silver in color. Do NOT use 

a bare copper lug, which is brown. 

Any grounding method and components listed 

according to NEC requirements are also acceptable in the US and Canada.

1

2

3
4

5

Cleaning

On principle, the modules do not need much cleaning if the tilt angle is sufficient  

(> 15°; self-cleaning by rain). If soiling occurs, we recommend cleaning the modules 

with plenty of water (hose) without the addition of cleaning agents but applicati-

on of a soft cleaning device (sponge). Never scrape or rub off dirt; this may result in 

micro-scratches.

 

Maintenance

We recommend regular inspections of the system to ensure that:

1.  All fixtures are securely tightened and corrosion-free;

2. Wiring is securely connected, properly arranged and free of corrosion;

3. Cables are free of damage;

Please also observe applicable standards. 

Disclaimer of liability

SolarWorld AG does not guarantee the operational capability and functionality 

of modules if the instructions contained in the present user information are not 

complied with. Since compliance with this guide and the conditions and methods 

of installation, operation, use and maintenance of the modules are not checked or 

monitored by SolarWorld AG, SolarWorld AG accepts no liability for damage arising 

through improper use or incorrect installation, operation, use or maintenance. Fur-

thermore, liability for infringements of patent law or of other third party rights ari-

sing from the use of the modules is excluded unless we are automatically liable by 

law.

Underwriters Laboratories Information (U.S. and Canada)

The solar module electrical characteristics are /-10% of the module label 

indicated values of Isc , Voc and Pmpp under Standard Test Conditions (irradiance 

of 100 mW/cm

2

, AM 1.5 spectrum, and a cell temperature of 25°C/77°F). Under nor-

mal conditions, a photovoltaic module is likely to experience conditions that produce 

more current and/or voltage than reported at standard test conditions. Accordingly, 

the values of Isc and Voc marked on this module should be multiplied by a factor of 

1.25 when determining component voltage ratings, conductor capacities, fuse sizes, 

and size of controls connected to the PV output. Refer to section 690-8 of the Natio-

nal Electric Code (NEC) for an additional multiplying factor of 125% (80% de-rating) 

which may be applicable.  Over-current protection shall be in accordance with the 

requirements of Article 240 of the NEC. Intended wire to be used: Listed PV Wire, 

AWG 12, outer diameter 7.1±0.2mm, rated min. 90°C dry/wet, 600V. PV Connectors: 

Type PV-KBT4/6II-UR and type PV-KST4/6II-UR are suitable for the output cable. Cab-

le conduits should be used in locations where the wiring is accessible to children or 

small animals. Modification or tampering of diodes by unqualified personnel is not 

permitted. Please consult a SolarWorld Service Center for additional information 

regarding diode replacement/repair. 

To reduce the operating temperature the module must be mounted with a minimum 

standoff height of 4 in (10 cm) above any surface.

In Canada the installation shall be in accordance with CSA C22.1, Safety Standard for 

Electrical Installations, Canadian Electrical Code, Part 1.

Suitable ambient conditions

The module is intended for use in moderate climatic conditions. The module must 

not be exposed to focused light. The module must neither be immersed in water 

or be exposed to continuous wetting (e.g. by fountains). Exposure to salt or sulfur 

(sulfur sources, volcanoes) implies a risk of corrosion. The module must not be used 

for maritime (e.g. boats) purposes. The module must not be exposed to extraordi-

nary chemical loads (e.g. emissions from manufacturing plants). If the modules are 

installed on stables, a distance of 3 ft/1 m to ventilation openings shall be ensured.

Appropriate usage

Make sure that the module meets the technical requirements of the overall system. 

Other system components should not exert any adverse mechanical or electrical 

influences on the module. Modules may bend under high loads. For this reason, 

sharp-edged mounting elements or other sharp objects (e.g. cable ties on mounting 

sections must not be mounted near the module back side. When wiring in series, use 

only modules of the same amperage rating, when wiring in parallel, use only modu-

les of the same voltage. The modules must not be operated at a higher voltage than 

the permissible system voltage. For system documentation, please note the model 

and serial number.

Optimum installation

In order to avoid performance losses, all modules connected in series should be 

arranged with the same orientation and tilt angle. The modules should be installed in 

an all-season shade free area. Even partial shading results in yield losses and should 

be avoided. Proper ventilation of the module underside will prevent heat build-up 

that reduces performance. Artificially concentrated sunlight shall not be directed on 

the module.

Mounting

The modules must be securely installed at a minimum of 4 locations on the frame. 

Mounting is only allowed in designated areas. These designated areas for mounting 

are located on the module long sides. They are located between 1/8 of the module 

length and 1/4 of the module length, measured from the module corner. Mounting 

the module on its narrow sides is not sufficient. In regards to “Top-Down” mounting 

methods, the maximum clamping pressure is 50 N/mm² (72.5 psi). Do not drill any 

holes into the module. Use corrosion-proof mounting material. For more details see 

mounting drawings and details shown on the last page.

Recommendation: Sunfix supporting profile, Sunfix (end) clamp 1.44 in (34 mm),  

frame tightening torque: 177 in-lb (20 Nm)

electrical connection

Use only rated copper solar wire and appropriate connectors. Ensure that they are 

in perfect electrical and mechanical condition.

 

Connectors may only be connected 

under dry conditions. Make sure to avoid loose connections in a plugged connection. 

Only singlecore solar wires may be used for connecting the modules. Wires should 

be attached to the installation system by means of UV-resistant cable ties. Exposed 

wires should be protected against sunlight and damage by suitable precautions (e.g. 

conduits). Check that wiring polarity is correct prior to commissioning the system.

Summary of Contents for Sunmodule SW xx poly RGA

Page 1: ...para el usuario Informations pour l utilisateur Sunmodule SW xxx poly R6A Sunmodule SW xx poly RGA Sunmodule SW xx poly RGP Sunmodule SW xx mono RHA Sunmodule SW xx poly RIB Sunmodule SW xx poly RMA S...

Page 2: ...den technischen Anforderungen des Gesamtsy stems entspricht Durch andere Anlagenkomponenten d rfen keine sch digenden mechanischen oder elektrischen Einfl sse auf das Modul ausge bt werden Module k n...

Page 3: ...les are not checked or monitored by SolarWorld AG SolarWorld AG accepts no liability for damage arising through improper use or incorrect installation operation use or maintenance Fur thermore liabili...

Page 4: ...mbras parciales provocan reduc ciones del rendimiento y por tanto deben evitarse La ventilaci n trasera evita una acumulaci n de calor que reduce la potencia Fijaci n Los m dulos tienen que fijarse de...

Page 5: ...me orientation et inclinaison afin d viter des pertes de puissance Les panneaux doivent tre install s un endroit sans ombrage pendant toute l ann e L ombrage m me partiel entra ne une r duction du re...

Page 6: ...en working on wiring use and wear protective equipment insulated tools insulated gloves etc Peligro Descarga el ctrica Si se conectan varios m dulos en serie las tensiones se suman y ello constituye u...

Page 7: ...r compared to the middle idle cable spring After engaged lid at top end push the lid over entire perimeter 1 3 Tighten cable gland to a torque of 11 5 13 3 lbf in 1 3 1 5 Nm to ensure IP65 pro tection...

Page 8: ...SolarWorld Africa Pty Ltd 24th Floor 1 Thibault Square Cape Town 8001 South Africa Phone 27 21 421 8001 Fax 27 21 421 8002 service solarworld africa co za www solarworld africa co www solarworld com...

Reviews: