10 • Mode Pages Display
________________________________________________________________________________________________
6.1
Parameter Setting
–
Temperature Settings
Press
▲ or▼
keys to set actual number of connected sensors
Range: 1-6 in TPR-6/6 and 1-14 in TPR-6/14.
Press
SELECT
Type of temperature sensor in temperature input x.
x represents any number between 1-6 in TPR-6/6 and any number between 1-14 in TPR-6/14.
Press
▲ or▼
keys to set actual type of sensors.
Sensor type must be modified via internal dip switches (Refer to section
8 page 20.) as well as via the
software.
Range: NOT USED, RTD, PTC THERMISTOR, NTC THERMISTOR
If more than one sensor is used (as set in parameter NO. OF SENSORS above) it will show T2 SENSOR
TYPE, T3 SENSOR TYPE .. etc.
Press
SELECT
Tx LEVEL 1 (represents T1 LEVEL 1, T2 LEVEL 1 etc...) is normally used to set an Alarm Level
If Tx SENSOR TYPE is set to RTD this display is in deg. C (Celsius degrees).
If Tx SENSOR TYPE is set to PTC-THERMISTOR or NTC-THERMISTOR this display is in kOHM.
Press
▲ or▼
keys to set Tx LEVEL 1 value
Range for RTDs: 5 – 250 deg. C.
Range for Thermistors: 0.5 – 25.0 kOHM
Press
SELECT
Tx LEVEL 2 (represents T1 LEVEL 2, T2 LEVEL 2 etc...) is normally used to set a Trip Level
If Tx SENSOR TYPE is set to RTD this display is in deg. C (Celsius degrees).
If Tx SENSOR TYPE is set to PTC-THERMISTOR or NTC-THERMISTOR this display is in kOHM.
Press
▲ or▼
keys to set Tx LEVEL 2 value
Range: 5 – 250 deg C
Press
SELECT
Time delay for Level 1 (for all sensor channels)
Press
▲ or▼
keys to set time delay
Range: 0.1 – 20 Sec.
TEMPERATURE
*** SETTINGS ***
NO. OF SENSORS
3
Tx SENSOR TYPE
RTD
rtd
Tx LEVEL 1
120 deg. C
rtd
TEMP. LEVEL 1 DELY
2.0 SEC.
Tx LEVEL 2
140 deg. C
rtd
Important Note:
In order to set the sensor type connected to the TPR-6 the Tx SENSOR TYPE parameter must
be set accordingly and dip switch setting must be done as well. Refer to section
8 page 20 for
dip switch settings.