Installation
7
77
7
WARNING
Cooling air of 100CFM on
the heat-sink fins must be
maintained at all times, or
your unit will shut down.
Installation
Environment
M o i s t u r e
Your converter should be kept dry at all times. The unit is factory sealed to withstand moisture, but is
not waterproof.
Use the following guidelines regarding placement of your unit:
•
Avoid locations were your unit will be routinely exposed to water.
•
Do not wash your unit with a pressure sprayer. Large amounts of water will cause a
malfunction.
•
If you have reason to believe water has entered the unit,
Do Not
open the case. Disconnect
your unit and return it for service as soon as possible. Units with extensive water damage
may not be repairable.
Units returned to Solectria with the factory seal broken will be
ineligible for warranty service.
C o o l i n g A i r R e q u i r e m e n t s
Ample airflow must be available to cool your converter. Your unit is forced-air cooled because this
gives greater overall electrical efficiency.
Your units’ performance and lifetime will both be reduced if cooling air is not
available. If your unit is running at a temperature of 75
°
C or greater, the output
current will be limited to 50% of the rated maximum.