Installation and Operation Manual (Rev B)
PVI 10KW, 13KW, 15KW
21
DOCR-060011
VAC Low
Reconnecting
Pac: XXXX W
Waiting for grid
Reverse phasing
& restart PVI!
Pac: XXXX W
Min Vmpp reached
AC Contact Open
978-683-9700
Vsense Err
978-683-9700
Open Phase
978-683-9700
MAG Failure
978-683-9700
Pac: XXXX W
PS Fail
Pac: XXXX W
PS Wake Fail
Pac: XXXX W
Lost Freq Lock
Pac: XXXX W
VDC Ctrl Fail
Pac: XXXX W
DMGI Overtemp
The inverter had a “UL event” and is
in the 5 minute wait period
Wait for the inverter to restart
Grid voltage may not be present
Check for grid voltage
The VAC grid connection phasing
does not match the inverter
Change the phase wire positions at the inverter
connection on the grid side
The power point tracking has been
reached
The max power point tracking has reached
minimum inverter operating voltage
The AC contactor is open when it is
being commanded to be closed
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be serviced
by an authorized service provider.
An internal failure of the voltage
sensing circuit has occurred
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be serviced
by an authorized service provider.
One of the AC phases is not present
at the inverter
Verify that there is AC voltage on all phases at the
inverter and all fuses are intact.
An internal failure of one of the
magnetic components
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be serviced
by an authorized service provider.
An internal failure of the power stage
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be serviced
by an authorized service provider.
The power stage did not initialize
properly
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be serviced
by an authorized service provider.
An internal failure of the voltage
sensing circuit
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be serviced
by an authorized service provider.
The DC voltage is outside of the
regulation specifications
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be serviced
by an authorized service provider.
The power stage has exceeded its
temperature limit
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be serviced
by an authorized service provider.