Installation
and
Operation
Manual
(Rev
A)
PVI
50
‐
100KW
Series
Inverters
DOCR
‐
070233
Page
20
of
92
The
table
below
pertains
to
the
standard
AC
disconnect
switches
without
fuses.
It
includes
requirements
for
the
AC
conductor
size,
the
number
of
terminals
available,
proper
terminal
torque,
and
AC
disconnect
switch
current
ratings
for
all
PVI
50
‐
100KW
inverter
models.
The
PE
models
use
the
same
AC
disconnect
switches
as
the
standard
models.
AC
VOLTAGE
INVERTER
MODEL
With
Unfused
AC
Disconnect
Switch
TERMINALS
PER
PHASE
WIRE
GAUGE
TERMINAL
TORQUE
DISCONNECT
SWITCH
SIZE
208V
PVI
50KW
208V
1
2/0AWG
‐
250kcmil
275
in
‐
lbs
200A
PVI
60KW
208V
1
4/0AWG
‐
250kcmil
275
in
‐
lbs
200A
PVI
75KW
208V
1
300kcmil
‐
750kcmil
500
in
‐
lbs
400A
2
1/0AWG
‐
300kcmil
500
in
‐
lbs
PVI
85KW
208V
1
350kcmil
‐
750kcmil
500
in
‐
lbs
400A
2
1/0AWG
‐
300kcmil
500
in
‐
lbs
PVI
100KW
208V
1
500kcmil
‐
750kcmil
500
in
‐
lbs
400A
2
2/0AWG
‐
300kcmil
500
in
‐
lbs
240V
PVI
50KW
240V
1
1/0AWG
‐
250kcmil
275
in
‐
lbs
200A
PVI
60KW
240V
1
3/0AWG
‐
250kcmil
275
in
‐
lbs
200A
PVI
75KW
240V
1
4/0AWG
‐
750kcmil
500
in
‐
lbs
400A
2
1/0AWG
‐
300kcmil
500
in
‐
lbs
PVI
85KW
240V
1
300kcmil
‐
750kcmil
500
in
‐
lbs
400A
2
1/0AWG
‐
300kcmil
500
in
‐
lbs
PVI
100KW
240V
1
350kcmil
‐
750kcmil
500
in
‐
lbs
400A
2
1/0AWG
‐
300kcmil
500
in
‐
lbs
480V
PVI
50KW
480V
1
4AWG
‐
250kcmil
275
in
‐
lbs
200A
PVI
60KW
480V
1
3AWG
‐
250kcmil
275
in
‐
lbs
200A
PVI
75KW
480V
1
2AWG
‐
250kcmil
275
in
‐
lbs
200A
PVI
85KW
480V
1
1AWG
‐
250kcmil
275
in
‐
lbs
200A
PVI
100KW
480V
1
1/0AWG
‐
250kcmil
275
in
‐
lbs
200A
600V
PVI
50KW
600V
1
6AWG
‐
250kcmil
275
in
‐
lbs
200A
PVI
60KW
600V
1
4AWG
‐
250kcmil
275
in
‐
lbs
200A
PVI
75KW
600V
1
3AWG
‐
250kcmil
275
in
‐
lbs
200A
PVI
85KW
600V
1
2AWG
‐
250kcmil
275
in
‐
lbs
200A
PVI
100KW
600V
1
1AWG
‐
250kcmil
275
in
‐
lbs
200A
Table
4.3
–
AC
Power
Conductor
Sizes
&
Torques
for
Standard
AC
Disconnect
Switches