7.6
Fuse
replacements
AC
Fuses
(if
equipped)
WARNING:
If
inverter
is
equipped
with
the
fused
AC
disconnect
switch,
fuses
must
only
be
replaced
with
600VAC
rated
fuses
of
the
same
type
and
rating
.
The
following
table
includes
current
ratings
of
fuses
provided
with
fused
AC
disconnect
switch
option
according
to
inverter
power
rating
and
AC
output
voltage.
Inverter
Model
AC
Voltage
PVI
‐
50KW
PVI
‐
60KW
PVI
‐
75KW
PVI
‐
75KW
‐
PE
PVI
‐
85KW
PVI
‐
85KW
‐
PE
PVI
‐
100KW
PVI
‐
100KW
‐
PE
208V
175A
225A
300A
300A
350A
240V
150A
200A
225A
300A
300A
480V
110A
110A
125A
150A
150A
600V
110A
110A
110A
110A
125A
Table
7.1
–
AC
Disconnect
Switch
Fuse
Specifications
DC
Input
Fuses
(if
equipped)
WARNING:
If
inverter
is
equipped
with
the
fused
PV
sub
‐
combiner,
fuses
in
DC
disconnect
switch
must
only
be
replaced
with
600VDC
rated
fuses
of
the
same
type.
Always
refer
to
PV
module
and
combiner
fuse
ratings
and
specification
before
selecting
or
replacing
fuses.
GFDI
fuse
WARNING:
Only
replace
GFDI
fuse
with
Bussmann
KLM
‐
2
(2A,
600
VDC
rated)
Other
Fuses
WARNING:
Unless
otherwise
specified,
only
replace
other
fuses
with
fuses
of
same
type
and
rating.
See
fuse
schedule
located
along
inverter
enclosure
interior
right
wall
for
complete
list
of
fuse
ratings
and
types.