PVI 3000/4000/5000/5300
Installation and Operation Manual
10
PVI 5000/PVI 5300 DIMENSIONAL DIAGRAM
73
2
454
184.2
94
45
125
250
70
19
0
175.5
Fig. 2.1 PVI 3000/4000/5000/5300 Dimensional Diagram
Placement and location
· PVI 3000/4000/5000/5300 inverters that must be vertically mounted may be located indoors or outdoors, given the NEMA
3R rating.
· Avoid mounting the inverter on a location where is exposed to direct rain.
· Leave at least 20” of free space above and 40” below the inverter for best ventilation (see Figure 2.1.1).
· Mount the inverter on a wall that is strong enough to support the 47-60lb inverter.
WARNING!
Some parts of the heatsink can reach temperature over 160F (70
℃)
. Keep flammable, explosive materials
or trash and unknown materials at an appropriate distance from the inverter!
WARNING!
Do not expose the inverter to corrosive liquids and/or gases.
· Keep AC and DC wiring as short as possible to minimize power loss.
· Mounting bracket should be fastened to a concrete or a masonry wall using appropriate anchors.
Conduit Locations, Pre-punched Holes and Knock-outs
· Holes are pre-punched (and shipped with hole covers) for 1” conduit fittings on the left and right sides of the wiring box,
these holes are centered at 2.5” from the wall mounting surface.
· ¾” and 1” concentric KOs are on the bottom of the AC and DC sides of the wiring box and these are located 2.63” from
the wall mounting surface.
· ¾” and 1” concentric KOs are on the back of the AC and DC sides of the wiring box for routing wiring out the back of the
box into the wall for a “hidden wiring” installation.
17.75”
28.82”
9.88”
4.94”
3.7”
1.75”
2.75”
7.5”
6.91”
7.25”