PVI 3000/4000/5000/5300
Installation
and Operation Manual
23
N terminal
L1 wire connected to
L1 terminal
L2 wire connected to
L2 terminal
Equipment ground wire
connected to ground bar
Fig 2.3.8
AC Terminal Block for AC cable connections
·
Connect the AC equipment GND wire to the screw of the ground bar labeled
·
Connect the white N wire to the terminal labeled N of the AC terminal block.
·
Connect the L1 wire to the terminal labeled Line1 of the AC terminal block.
·
Connect the L2 wire to the terminal labeled Line2 of the AC terminal block.
·
Tighten the screws with a torque of 15.6 in-lb (1.7Nm)
WARNING!
Each connection to a PVI 3000-5300 inverter must be installed with a dedicated circuit breaker with 20-30
amperes (depending on inverter model) maximum branch circuit over current protection in accordance
with the National Electric Code, ANSI/NFPA 70. No other appliances may be connected to the circuit
breaker.
·
Reconfirm that all connections are correct as described above and all screws are properly tightened.
Connection of the DC wiring
The wiring box of the PVI 3000-5300 inverter is designed with a pair of the DC terminal blocks which support up to four
(4) independent PV strings to be fused and connected in parallel in the wiring box and then feed into the inverter (or 3 in the
case of the PVI 3000). The PVI 3000-5300 inverter is shipped with up to four (4) 15A, 600Vdc PV string fuses in the wiring
box for the PV strings. However, the size of the PV string fuses shall be determined by the electrical ratings of the PV
module and by UL and National Electrical Code (NEC) requirements. Please refer to Figure 5.2 for the replacement of the
PV string fuses. 15A fuses are shipped standard with every inverter unless other values are specified at the time of order. 8,
10 and 12A values are also available from the factory. The fused combiner also is bypassed using the provided bypass
terminals (2 positions).
There are two (2) terminals, labeled “Ungrounded (+)” and “Grounded (-)”, per PV string located in the wiring box used
for the DC connections as shown in Figure 2.3.9 The DC equipment ground wire shall be connected to a screw on the
ground bar labeled
in the wiring box of the PVI 3000-5300 inverter. All the screws shall be tightened with a torque of
15.6 in-lb (1.7Nm)
Fig 2.3.9
DC terminal blocks for DC wiring connections
Connect to PV+
Connect to PV-
Connect to PV+
if fuse bypass is
desired