Installation
and Operation Manual
33
3 seconds
↓
Then the LCD will display the setting of the AC high voltage limit above which value, inverter will reduce the output power
until the AC voltage drops within this setting. If the grid type is set to 208/240 with neutral, then the display will be looked
as the figure shown below.
3 seconds
↓
Then the setting of the re-connection time will be displayed. The re-connection time is the duration of delay time for the
inverter to re-connect to the grid after the fault(s) is(are) cleared.
3 seconds
↓
Waiting Mode Display
After the basic information of the inverter is displayed, the system enters the
System Check mode
which is indicated on the
LCD.
During the system checking, if the DC input voltage is not reaching the point of the PV start voltage setting, , then the
following message will be shown on the LCD and the system will stay at this step.
During the system checking, if the grid is not connected to the inverter, then the inverter enters the fault mode and the
following message will be shown on the LCD.
Once system check is done, the inverter goes into the
monitoring mode
. If all data needed for grid feeding is in the acceptable
range, the system will keep monitoring this data for a period of time. The following information tells users that the system will
go into the grid feeding mode in XXX seconds and then show the measured data of the DC input voltages and the existing
voltage and frequency on the grid side.
L o w I n s o l a t i o n
V a c H L i m i t
L - N X X X . X V
V p v S t a r t X X X . X V
R e c o n n e c t X X X s
F a c L X X . X X H z
C l r t < X X X C y c s
M o d e F a u l t
G r i d N A
M o d e
S y s t e m C h e c k i n g