PVI 3000/4000/5000/5300
Installation
and Operation Manual
41
VacL2 L
MOV Fault, AC
MOV Fault, DC
GFDI
DCInjectCurH
VdcbusH
Internal COMM
Watchdog
Idc Test
Offset
Temp. Sensor
RAM Test
EEPROM Test
System Error
Version Error
CPU Delta Fac
CPU Delta Vac
CPU Delta GFDI
CPU Delta Idc
IpvH
Driver Fault
CalDataError
CalDataLoss
Ibuck Over
Converter Error
The voltage between L2 and neutral is under the lower limit.
High voltage protection function failed on the AC side.
High voltage protection function failed on the DC side.
The GFDI Fuse is open or blown.
Too much DC current injected into the AC grid is detected.
Internal DC bus voltage is above the upper limit.
Internal communication failed.
Internal watchdog function triggered.
The DC injection current monitoring function failed.
Offset check for grid monitoring failed.
The internal temperature sensor failed.
Memory failed
EEPROM test failed.
The system failed.
The firmware version is not correct.
Internal measurement comparison error or defective hardware
Over current on the DC side
Driver circuit or power device failed
Calibration data is out of range
Calibration data is lost.
Internal converter over current
DC/DC hardware failed.
Maintenance:
Replacing the GFDI Fuse
Remove the cap of the GFDI fuse holder to open and then replace the GFDI fuse with the same type and rating (600VDC, 1A).
Before replacement of the fuse, you must switch off the DC/AC disconnect switch and AC breaker and wait for at least 5
minutes for system to discharge.