PVI 3000/4000/5000/5300
Installation and Operation Manual
42
GFDI Fuse
OPEN
Fig 5.1 Open the cap of the GFDI fuse holder
WARNING!
For continued protection against risk of fire, replace only with the same type and ratings of fuse (600
VDC, 1 A)!
Replacing of the PV String Fuses
The inverter is shipped with four (4) 15A, 600Vdc PV string fuses for PV strings (or three for PVI 3000). However, the size of
the PV string fuse is determined by the electrical ratings of the PV module and by UL and National Electrical Code (NEC)
requirements. The minimum size of the PV string fuse is calculated using the short circuit current rating (Isc) of the PV
module. The NEC requires that the fuse be sized for a minimum of 1.56 times the Isc of the PV module used in the system and
not over the module’s fuse rating. Please be sure to consult with the PV module manufacturer for appropriate PV string fuse
rating.
Fig 5.2 Replacement of the PV string fuses
WARNING!
PV arrays is always energized when exposed to light therefore hazardous voltage is still present on the
terminal blocks and the PV string fuse holders even the DC/AC disconnect switch is switched OFF.
Please cover the PV arrays with opaque (dark) materials during PV string fuse replacement.
1.
Turn OFF all DC/AC disconnect switch and AC
breaker
2.
Wait for at least 5 minutes
3.
Exchange the fuses
4.
Turn ON all DC/AC disconnect switch and AC
breaker
1. Turn OFF all DC/AC disconnect switch and
AC breaker.
2. Wait for at least 5 minutes.
3. Remove the cover of the wiring box by
following the steps described in section 2.3.
4. Replace the fuses as shown in the figure 5.2.
5. Put the cover of the wiring box back and fasten
the screws.
6. Turn ON all DC/AC disconnect switch and AC
breaker.