PVI 3000/4000/5000/5300
Installation and Operation Manual
48
Output to AC grid connection:
The PVI 3000-5300 is designed to feed power into a standard 60Hz, 240 or 208V AC utility service or 208V AC provided
within a facility by a step down transformer (for example, from 480V AC service). As required by NEC, there must be a
dedicated 2-pole circuit breaker for the PV inverter connection. This circuit breaker (and wiring) must have a rating of 20, 25
or 30A depending on the model. The inverter is designed to work with the range of AC voltage for a 240VAC or 208V
service defined by UL1741/IEEE1547.
AC Output of PVI 3000-5300
0
1000
2000
3000
4000
5000
6000
200
250
300
350
400
450
500
550
600
DC Input Voltage (VDC)
AC Output
Power (W)
PVI 3000
PVI 4000
PVI 5000
PVI 5300
“strike” voltage (235VDC)
Fig. 7.2 AC Output power of PVI 3000-5300
Fig. 7.3 Serial Number Key (description)
PVI 5300
PVI 5000
PVI 4000
PVI 3000