Fig D2
Negative Ground Setting and Vdc wires connections
UNGROUNDED
CONDUCTOR
GROUNDED
CONDUCTOR
UNGROUNDED
CONDUCTOR
GROUNDED
CONDUCTOR
N
e
ga
tiv
e
gr
ound
1
1
P
o
s
itv
ie
gr
ound
connect to PV+
connect to PV-
Fig D3
DC terminal blocks for DC connections in Negative Ground Systems
CAUTION!
Polarities of each DC input from a PV string shall be correctly connected to the “Ungrounded (+)”
(positive) and “Grounded (–)” (negative) terminals of a pair respectively. The DC voltage must be less
than 600V in any condition.
The “Ungrounded (+)” wire of the DC input shall be connected to the terminal labeled “Ungrounded (+)” and the
“Grounded (-)” wire of the DC input shall be connected to the terminal labeled “Grounded (-)”.
· Avoid using wire nuts to join any wires together or to make any connections in the PV system. Wire nuts are a frequent
cause of unreliable connections, resistive connections, and ground faults.
· Connect the equipment ground cable to the screw of the ground bar labeled .
· Tighten the screws with a torque of 15.6 Lb-in (1.7Nm).
Black wire connected to
Grounded, DCIN-
Red wire connected to
Ungrounded, DCIN+