PVI 3000/4000/5000/5300
Installation
and Operation Manual
53
!
!
P
o
s
itv
ie
gr
ound
N
egat
iv
e
gr
ound
11
connect to PV+
UNGROUNDED
CONDUCTOR
GROUNDED
CONDUCTOR
Fig D5
DC terminal blocks for DC cable connection in Positive Ground
CAUTION!
The Positive Polarities of the DC input from a PV strings shall be correctly connected to the original
“Grounded (-)” (negative) terminals (re-labeled “Grounded (+)”) and the Negative Polarity of the DC
input from a PV string shall be connected to the original “Ungrounded (+)” (positive) terminals (re-labeled
“Ungrounded (-)“). The DC voltage must be less than 600V in all conditions.
· Avoid using wire nuts to join any wires together or to make any connections in the PV system. Wire nuts are a frequent
cause of unreliable connections, resistive connections, and ground faults.
·
Connect the equipment ground wire to the screw of the ground bar labeled .
·
Tighten the screws with a torque of 15.6 lb-in (1.7Nm).
CAUTION!
PV arrays are energized when ex-posed to light. Use safe working practices when working on PV arrays.
WARNING!
Route the DC connection cables to the inverters away from any possible hazards that could damage the
cables.
WARNING!
Hazardous voltage is still present on the device after is it disconnected from all PV DC inputs. Allow 5
minutes for the inverter to discharge the energy completely.
· Up to four (4) independent PV strings (4 pairs) can be connected to the inverter as shown in the figure 3C. The PV strings
are connected in parallel in the wiring box. Therefore, these four (4) PV strings shall be the same in capacity, especially
each total string voltage.
N
PV+
PV-
L2
L1
Fig D6
PV- terminal connection