2.0 Site Preparation and Inverter Placement
The inverter is comprised of a rainproof NEMA 3R industrial enclosure containing electrical and
electronic components.
NOTE:
If the inverter is mounted outside, during the installation process and in case of
rain, do not open the inverter.
Criteria for device mounting:
•
Because the inverter is in a NEMA 3R enclosure, the inverter can be mounted outdoors.
•
The longest inverter life can be achieved by mounting it in a clean, dry and cool location. It is
recommended to keep the unit out of direct rain or snow. Protection by a roof overhang or
covering is recommended if outdoor mounting is necessary.
•
For optimal electrical system efficiency, use the shortest possible AC and DC cables and use
the maximum allowable cable size.
•
Avoid installation in close proximity to people or animals, as there is an audible high-
frequency switching noise.
•
Install the inverter in an accessible location following local codes. Note that code
requirements for clearances and proximity to other equipment and building walls apply.
•
For optimal inverter life and performance, do not mount the inverter in direct sunlight,
especially in hot climates. If the unit must be mounted in direct sunlight, a silver or white
metal sun-shield is highly recommended. It is further recommended that the inverter be
mounted on the north or east side of buildings or on the northern side of a ground mounted
PV array. Following these guidelines help prevent the unit from limiting the power produced
due to an excessively high inverter temperature.