PVI 3000S, 4000S, 5000S, 5300 Series Inverters
Installation and Operation Manual (Rev A)
33
Figure 4.4.3 – RS-485 Connection
Description
Part Number
Typical Use
Length
Cable, RS485 comm. PVI 3000S-
5300
WIH-020082
RS485 cable for communication
gateways
7 ft
Cable, RS485 daisy chain PVI
3000S-5300
WIH-020081
RS485 jumper cable, for 3000S-
5300 inverter-to-inverter
30 in.
Table 4.4.4 – Standard Cables available for RS232 and RS485 communication
4.5
Communication ID Adjustment
When using SolrenView data monitoring use an address between 1 and 16. SolrenView can
automatically detect the ID# (see SolrenView manual). Each inverter requires a unique number
when connected to a single communication DAS. The inverter terminator resistor should be
turned off except for the inverter furthest away from the Solrenview gateway, i.e. the last
inverter on the end of the line.
5.0 Commissioning the Inverter PV System
At this point the inverter should be mounted, all connections are made and you are ready to
power it up.
WIH-020081
RS485 Daisy
chain
To gateway or
computer WIH-
020082