PVI 3000S, 4000S, 5000S, 5300 Series Inverters
Installation and Operation Manual (Rev A)
49
Error
Message
Description
Possible Solutions
GridNA
No AC voltage is detected.
Verify AC voltage disconnect on
Verify AC circuit breaker is
on/operational
Verify and measure AC voltage
present in Inverter disconnect
Contact installing company or
Solectria Renewables
Drift Fac
Islanding is detected.
Verify AC voltage present and
correct in Inverter disconnect
Contact installing company or
Solectria Renewables
VacH
The AC voltage of utility is above the
upper limit.
Verify setting for S201 is correct
for the grid voltage applied
Measure the AC voltage and
compare to the voltage on the
inverter display
Contact Solectria Renewables for
assistance if the range needs to
be adjusted
VacL
The AC voltage of mains utility is below
the lower limit.
Verify setting for S201 is correct
for the grid voltage applied
Measure the AC voltage and
compare to the voltage on the
inverter display
Contact Solectria Renewables for
assistance if the range needs to
be adjusted
FacH
The frequency of AC voltage of the
utility is above the upper limit.
Measure the frequency and
compare to the frequency on the
display
Contact Solectria Renewables for
assistance if the range needs to
be adjusted
FacL
The frequency of AC voltage of the
utility is below the lower limit.
Measure the frequency and
compare to the frequency on the
display
Contact Solectria Renewables for
assistance if the range needs to
be adjusted
VpvH
The DC voltage of PV array is above the
upper limit.
Turn off the inverter
Measure the VDC at the Inverter
disconnect if over 599VDC the