PVI 3000S, 4000S, 5000S, 5300 Series Inverters
Installation and Operation Manual (Rev A)
50
solar array needs to be inspected
Contact installing company
Do not turn on the inverter until
the condition is repaired
Imax_AC
Over current on the AC side.
The inverter will continue to
operate at a lower current
If message occurs frequently
contact the installing company
InvTempMax
The internal temperature of the
inverter exceeded the safe operating
limit.
If the inverter is located in direct
sunlight it may need to be
shaded
The VDC input may be too high
causing increased temperature,
reduce VDC input. Contact
installing company or Solectria
Renewables
Relay Open
Relay Close
Relay test failed.
Contact installing company or
Solectria Renewables
VacL1 H
The voltage between L1 and neutral is
over the upper limit.
Verify setting for S201 is correct
for the grid voltage applied
Measure the AC voltage and
compare to the voltage on the
inverter display
Contact Solectria Renewables for
assistance if the range needs to
be adjusted
VacL1 L
The voltage between L1 and neutral is
under the lower limit.
Verify setting for S201 is correct
for the grid voltage applied
Measure the AC voltage and
compare to the voltage on the
inverter display
Contact Solectria Renewables for
assistance if the range needs to
be adjusted
VacL2 H
The voltage between L2 and neutral is
over the upper limit.
Verify setting for S201 is correct
for the grid voltage applied
Measure the AC voltage and
compare to the voltage on the
inverter display
Contact Solectria Renewables for
assistance if the range needs to
be adjusted
VacL2 L
The voltage between L2 and neutral is
under the lower limit.
Verify setting for S201 is correct
for the grid voltage applied