PVI 3000S, 4000S, 5000S, 5300 Series Inverters
Installation and Operation Manual (Rev A)
51
Measure the AC voltage and
compare to the voltage on the
inverter display
Contact Solectria Renewables for
assistance if the range needs to
be adjusted
MOV Fault,
AC
High voltage protection function failed
on the AC side.
Verify MOV appearance is OK
Measure MOV using diode
function of DMM if shorted
contact Solectria Renewables
MOV Fault,
DC
High voltage protection function failed
on the DC side.
Verify MOV appearance is OK
Measure MOV using diode
function of DMM if shorted
contact Solectria Renewables
GFDI
The GFDI Fuse is open or blown.
DO NOT TOUCH any equipment
(including, but not limited to: the
inverter, the PV array
disconnects, the PV array
combiners, the PV panels, the PV
racking system). Immediately
contact the installer or another
qualified person to locate and
repair the source of the ground
fault.
DCInjectCurH
Too much DC current injected into the
AC grid is detected.
Turn off the inverter and restart.
If the error re-occurs Contact
installing company or Solectria
Renewables
VdcbusH
Internal DC bus voltage is above the
upper limit.
Turn off the inverter and restart.
If the error re-occurs Contact
installing company or Solectria
Renewables
Internal
COMM
Internal communication failed.
Internal watchdog function triggered.
Turn off the inverter and restart.
If the error re-occurs Contact
installing company or Solectria
Renewables
Watchdog
Internal watchdog function triggered.
Turn off the inverter and restart.
If the error re-occurs Contact
installing company or Solectria
Renewables
Offset
The DC injection current monitoring
function failed.
Turn off the inverter and restart.
If the error re-occurs Contact
installing company or Solectria
Renewables