PVI 3000S, 4000S, 5000S, 5300 Series Inverters
Installation and Operation Manual (Rev A)
53
Ibuck Over
Internal converter over current
Turn off the inverter and restart.
If the error re-occurs Contact
installing company or Solectria
Renewables
Converter
Error
DC/DC hardware failed.
Turn off the inverter and restart.
If the error re-occurs Contact
installing company or Solectria
Renewables
Table 7.1.1 – LCD Error messages
7.2 Maintenance
Replacing the GFDI Fuse
Remove the cap of the GFDI fuse holder to open and then replace the GFDI fuse with the same
type and rating (600VDC, 1A). Before replacement of the fuse, you must switch off the DC/AC
disconnect switch and AC breaker and wait for at least 5 minutes for system to discharge.
GFDI Fuse
OPEN
Figure 7.2.1 – Open Cap to Access the GFDI Fuse
Replacing the PV String Fuses
The inverter is shipped with four (4) 15A, 600Vdc PV string fuses for PV strings (or three for PVI
3000S). However, the size of the PV string fuse is determined by the electrical ratings of the PV
module and by UL and National Electrical Code (NEC) requirements. The minimum size of the PV
string fuse is calculated using the short circuit current rating (Isc) of the PV module. Please be
sure to consult with the PV module manufacturer for appropriate PV string fuse rating.
IN NO
CASE SHALL FUSES OF LARGER THAN 15A BE USED FOR THE PV STRING FUSES.