Installation and Operation Manual (Rev E)
SGI Series Inverters
DOCR-060371
38
DC GND Fault
Check DC Wiring
VAC Low
Reconnecting
Pac: XXXX W
Waiting for grid
Reverse phasing
& restart PVI!
Pac: XXXX W
Min Vmpp reached
AC Contact Open
978-683-9700
Vsense Err
978-683-9700
Open Phase
978-683-9700
MAG Failure
978-683-9700
Pac: XXXX W
PS Fail
Pac: XXXX W
PS Fail (Slave)
Pac: XXXX W
PS Wake Fail
Pac: XXXX W
Lost Freq Lock
Pac: XXXX W
VDC Ctrl Fail
Pac: XXXX W
DMGI
Overtemp
A ground fault has been detected in
the PV array
DO NOT TOUCH any equipment (including, but
not limited to: the inverter, the PV array
disconnects, the PV array combiners, the PV
panels, the PV racking system). Immediately
contact the installer or another qualified
person to locate and repair the source of the
ground fault.
The inverter had a “UL event” and is
in the 5 minute wait period
Wait for the inverter to restart
Grid voltage may not be present
Check for grid voltage
The VAC grid connection phasing does
not match the inverter
Change the phase wire positions at the
inverter connection on the grid side
The power point tracking has been
reached
The inverter will hold the Vmpp at this
level until it increases.
The AC contactor is open when it is being
commanded to be closed
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be
serviced by an authorized service provider.
An internal failure of the voltage
sensing circuit has occurred
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be
serviced by an authorized service provider.
One of the AC phases is not present at
the inverter
Verify that there is AC voltage on all
phases at the inverter and all fuses are
intact.
An internal failure of one of the
magnetic components
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be
serviced by an authorized service provider.
An internal failure of the master
power stage
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be
serviced by an authorized service provider.
An internal failure of one of the slave
power stages
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be
serviced by an authorized service provider.
One of the internal power stages did
not initialize properly
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be
serviced by an authorized service provider.
An internal failure of the voltage
sensing circuit
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be
serviced by an authorized service provider.
The DC voltage is outside of the
regulation specifications
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be
serviced by an authorized service provider.
One of the internal power stages has
exceeded its temperature limit
Turn off the inverter and contact Solectria
Renewables. The inverter may need to be
serviced by an authorized service provider.