Installation and Operation Manual (Rev E)
SGI Series Inverters
DOCR-060371
47
9.2
Output AC Specifications
The inverters are designed to feed power into a standard 60Hz, three-phase AC utility service
provided within a facility by a transformer with a rating of not less than the rating of the
inverter(s) connected to it.
As required by NEC, there must be a dedicated three-phase circuit breaker for the PV inverter
connection.
The inverter is designed to work with the range of AC voltages for a three-phase service defined
by IEEE 1547-2003 and ANSI C84.1.
SGI 225
SGI 250
SGI 266
SGI 300
SGI 500/
500PE
Unit
Operating AC voltage range
88 – 110%
VAC
Turn-on AC voltage range
92% – 105%
VAC
Default over/under voltage trip points
and times
per IEEE Std 1547-2003, Table 1 or utility specific order
codes
Over voltage trip magnitude adjustability
100% - 120%
V
nom
Under voltage trip magnitude
adjustability
50% - 100%
V
nom
Over / under voltage trip time
adjustability
0.1 – 30
sec
Voltage measurement accuracy
+/- 2 %
Operating frequency adjustability
(60) -3.0 - +0.5
Hz
Under frequency trip time adjustability
0.16 – 300
sec
Frequency measurement accuracy
+/- 0.1
Hz
Maximum Rated Output Current
(208VAC) external transformer
624
693
738
832
1388
A
rms
Maximum Rated Output Current
(208VAC) internal transformer
624
693
738
N/A
N/A
A
rms
Maximum Rated Output Current
(480VAC)
271
301
320
360
602
A
rms
Maximum Rated Output Current
(600VAC)
217
240
256
289
480
A
rms
Short Circuit Current Contribution
Utility Short Circuit Current Output
(480VAC)
duration of 10 line cycles
271
301
320
360
602
A
rms
Peak Short Circuit Current Output
(480VAC)
duration of less than 300
microseconds
27
36
36
36
60
kA
pk
AC current measurement accuracy
+ / - 3%
AC real power and energy
measurement accuracy
+ / - 5%