FOR
PVI
3800-7600TL
9
Rapid Shutdown Combiner Installation and Operation Guide (Rev B)
DOCR-070566-B
NOTICE
- Using a power screwdriver to tighten the mounting hardware is not
recommended due to the risk of thread galling.
Check that the RSD Combiner is mounted securely on the PV racking.
CAUTION
- Do not bend the bracket of RSD Combiner.
NOTICE
- Stainless steel hardware should be used since the RSD combiner is
installed outdoors.
5.2
Opening the cover of RSD combiner
Remove the 4 M4 cover screws with a T20 Torx screw driver. To replace the cover
screws use a torque of 16 in-lbs (1.8 Nm).
WARNING
- Ensure no live voltages are present on PV input and output circuit
before RSD Combiner installation.
5.3
Grounding
The Solectria RSD Combiner has an external threaded grounding point for bonding
to the racking system. The required equipment ground for this device shall be
connected to the threaded grounding point located inside the enclosure.
Fig.5 Grounding of Solectria RSD Combiner