9
ENGLISH
ENGLISH
The models in this range offer the possibility of working as hot/cold air curtains.
We advise you to check that the unit is in perfect condition when unpacking it, as any manufacturing or quality
defect is covered by the S&P guarantee.
IMPORTANT: SAFETY GUIDELINES
The appliance must not be right above or below a socket.
Do not cover the unit with clothes or objects that may obstruct the airflow and cause overheating.
While in operation, the connection cable must not be in front of the air outlet.
If it is installed in the bathroom, it must be placed so that the switches or other devices of command cannot
be touched for a person that be in the bathtub or shower.
There must not be any inflammable objects at less than 50 cm from the unit (such as window curtains, etc.).
Keep the inlet and outlet grilles clean. When cleaning them, disconnect the unit from the main supply.
Do not manipulate the unit with wet hands.
The installation work must be carried out by an electrician.
IMPORTANT:
THIS APPLIANCE MUST BE EARTHED.
The means of disconnection from the mains supply must have an opening distance of at least 3 mm in all
poles.
To operate the unit as an Air Curtain, the maximum distance to the floor must not be greater than 3 m.
The minimum distance between the Air Curtain and the floor must be 1,8 m.
INSTALLATION
The unit must be fixed to a convenient surface, and the minimum distances shown on Fig. 1 must be kept.
To install the unit, proceed as follows:
If the spiral nuts already placed in the device are used, there must be marked the centers of
the screws (M-8) according to the table of Fig.2 (a) and Fig.2 (b). If the hanging fixation is used, the centers
must be marked according to the table of Fig.3 (a) and Fig.3 (b) and place the screws (D) and the set squares
(E). Then hang the device and to fix on the lowest part with the screw (G).
When the included wall bracket kit is used Fig. 4 (2 pcs. for 1000 models and 3 pcs. for 1500/2000 models)
set the support (L) to the back part of the curtain with the screws provided (I). Fix the brackets (J) to the wall
to match with the brackets on the curtain (L). See dimensions Fig. 3 (a) and Fig 3 (b). Then hang the device
and fix on the lowest part with the screw (K).
To access the connection cards you must open the front grille.
The maximum working pressure of the water radiator must not exceed 4 Kg/cm
2
.
The maximum temperature of the hot water must not exceed 95ºC.
The water coil must not operate at temperatures of less than 5ºC. When there is a risk of the temperature
dropping below this limit antifreeze liquid must be used or the installation must be emptied.
The water pump must be connected to the coil via the 1/2” gas thread inlets fitted for this purpose.
ELECTRICAL CONNECTION (FIG. 5)
The COR Air Curtains are installed appliances. When installing these air curtains, the standards and regula-
tions in force in your country must be followed strictly adhered to. Within the installation an electrical isolation
switch must be present, to enable the installer to cut all supply lines.
Connect the unit to the mains supply, checking that the voltage and frequency are the same as those indica-
ted on the electrical rating plate. Use the cables with the number of wires and sections as indicated on the
wiring diagram for every model.