1.800.627.4499
4
RENEWAIRE.COM
1.800.627.4499
11
10
FOR THE MOST COMPLETE AND CURRENT INFORMATION VISIT
RENEWAIRE.COM
SPECIFICATIONS & DIMENSIONS
Specifications may be subject to change without notice.
INDOOR UNIT
SPECIFICATIONS
Ventilation Type:
Static plate, heat and humidity transfer
Typical Airflow Range:
40-110 CFM
Unit is HVI Tested/Certified per CSA C439
Protocol:
Using one L-35 G5 Core
Standard Features:
Galvanized cabinet
Terminal strip hard wiring in ebox (no line cord)
Unit may be mounted in any orientation
Cross-core differential pressure ports
Control:
Can use any switched line-voltage power supply
(no low-voltage controls)
Filters:
Total qty. 2, MERV 8, spun-polyester media:
9 5/8" x 10 1/2" x 1"
Unit Dimensions: & Weight
22 1/2" L x 11 3/4" W x 23 3/4" H
36 lbs.
Max. Shipping Dimensions & Weight (in carton):
29" L x 22" W x 15" H
40 lbs.
Motor(s):
Qty. 2, Standard motorized impeller blowers
Accessories:
Backdraft damper 6
"
, 8"
Automatic balancing damper 4", 5", 6"
Louvered wall vent 6
"
- white, brown
120V line voltage Honeywell control
MERV 13 filter - OA airstream
Electric duct heater - RH series (1-11.5 kW);
designed for indoor ductwork installation only
5 7/8" Typ.
12 1/4" Overall (with Hanging Bracket)
18" Case
2 1/4" Typ.
22 1/2"
Overall
Power Wiring
Inlet 7/8"
6 1/4" Typ.
11 3/4" Typ.
5 3/4"
Typ.
OA
EA
RA
FA
Pressure Ports
(4) Typ.
11 5/8"
Case
23 3/4" Overall
10 1/8" Minimum
Service Area
(Door can be
Removed from
Hinges.)
22 1/4" Minimum
Service Area
21 1/4"
Door
Swing
2 5/8"
7/8" Typ.
21 7/8" Case
6" Nominal
Typ.
8" Nominal
Typ.
25 1/2" Overall
(with Hanging bracket)
Formed
Inlet Ring
LEFT VIEW
FRONT VIEW
RIGHT VIEW
TOP VIEW
Model: GR90
Drawing Type: Unit Dimension
Version: JUN18
ABBREVIATIONS
EA: Exhaust Air to outside
OA: Outside Air intake
RA: Room Air to be exhausted
FA: Fresh Air to inside
INSTALLATION ORIENTATION
Unit may be installed in any
orientation.
NOTE
1.UNLESS OTHERWISE SPECIFIED,
DIMENSIONS ARE ROUNDED TO THE
NEAREST EIGHTH OF AN INCH.
2.SPECIFICATIONS MAY BE SUBJECT
TO CHANGE WITHOUT NOTICE.
UNIT DIMENSIONS
AIRFLOW ORIENTATION
Available as shown in dimension drawing.
UNIT MOUNTING & APPLICATION
Can be mounted in any orientation. RA/EA airstream
can be switched with OA/FA airstream.
ELECTRICAL DATA
HP
Volts
HZ
Phase
Input Watts
FLA
0.03
120
60
Single
46 @ 90 CFM
0.35
CORE PERFORMANCE
Airflow CFM
Temp EFF%
Total EFF%
Winter/Summer*
36
78
75/65
52
74
69/58
67
70
65/53
81
67
61/49
94
64
58/45
108
61
55/42
Note:
Indirect Gas-Fired Duct Furnace is not available on the GR90.
90
GR
Energy Recovery Ventilator
Standard
Download specification at:
renewaire.com/specifications
UNIT PERFORMANCE
Airflow CFM
ESP in H
2
0
36
0.60
52
0.50
67
0.40
81
0.30
94
0.20
108
0.10
Note:
These are core-only ratings and are not HVI certified.
HVI ratings apply to complete units only.
See HVI certification ratings on pg. 24 of Single/Multi-Family Catalog.