7.2.4 Countercurrent plate heat exchanger
•
The countercurrent plate heat exchanger is generally maintenance-free.
>>
Check the rotational direction of the bypass damper (Bypass, HR mode).
7.2.5 Quick heat-up (boost function)
>>
Check quick heat-up mode.
•
Extract air is fed back directly into the room via the boost damper.
•
In order to achieve the required set room temperature as quickly as possible, the air temperature is raised to a
maximum via a reheating coil.
•
All outdoor air dampers and exhaust air dampers are completely closed.
•
Extract air fan out of action.
•
The supply air fan is running and delivers the required flow rate.
•
When the set room temperature has been achieved, the unit switches to standard control mode.
7.3 Flow rate calculation
>>
The flow rate is calculated using the effective pressure method.
•
Compare the static pressure upstream of the inlet nozzle with the static pressure in the inlet nozzle.
•
The flow rate is calculated on the basis of the effective pressure Δp w (differential pressure of the two static pressures)
using the following equation:
•
The doors must be closed to determine the correct flow rate.
•
Feed the test houses to the outside (e.g. CPL-A through the exhaust air aperture, CPL-iH and CPL-iV through the base).