34
SOLID AIR ® INTERNATIONAL
•
T +31 598 36 12 21
•
www.solid-air.com
•
contact@solid-air.nl
8. MAINTENANCE
8.1 General information about maintenance
DANGER
Risk of electrical voltage even when the ON/OFF switch is set to OFF!
Danger of death from electrocution.
>>
Do not touch the EC fans for five minutes after disconnecting the power across all poles.
>>
Use a rubber mat if working on the unit when it is electrically charged
WARNING
Risk from rotating parts!
Risk of injury due to rotating fans or moving dampers.
>>
Secure the unit isolator to prevent restarting.
>>
Only open the inspection doors after the fans have come to a complete stop.
8.2 Maintenance shutdown
Fig. 8.1CPL maintenance
1
Unit isolator
2
Inspection door closures
>>
Regularly check that the ventilation unit is functioning correctly.
>>
Shut the system down using the unit isolator and safeguard against restarting.
8.3 Servicing the equipment
8.3.1 Compact filter
The compact filters are not renewable.
>>
Compact filters must be replaced when they are dirty or no later than after 12 months.
>>
Wear a suitable dust mask.
>>
Remove the compact filters from the unit casing once the right-hand inspection doors have been opened (see spare parts).
>>
Dispose of the dirty air filters in accordance with local regulations.
NOTE
Operation without filter
Contamination or damage of heat exchanger, fan and duct system
>>
The appliance may only be operated with the designated filters.
i