Legenda XE1 en XE2
No.
FeBeSy
Symbol
Description
5)
aGAxWP
Onsite heat pump (special equipment):
XE2: 1-2 : Heating/cooling signal heating pump 0-10V.
XE2: 3-4 : Heat pump fault (floating NC contact).
XE1: 1-2 : Cooling demand at heat pump (floating NO contact).
XE1: 3-4 : Heating demand at heat pump (floating NO contact).
Only present/available for the following unit designs:
- Systems with onsite heat pump.
5!
sKoxBM
Fire alarm system contact (special equipment)
(Note: Insert jumper if component is not present).
Only present/available for the following unit designs:
- Systems which are fitted with the “fire alarm system contact” when ordered.
Systems on which the “fire alarm system contact” was retrofitted.
5@
aGKxDV
Fault message contact for cooling system:
(Note: Insert jumper if component is not present).
Only present/available for the following unit designs:
- Systems that make use of a direct evaporator for the cooling function.
C
NC