6.4 Installing the outdoor unit
•
Weatherproof units must not be used for any load-bearing building functions or as a replacement for any
part of the roof (VDI 3803 5.1/DIN EN 13053 6.2).
>>
The outdoor unit must be placed on a level horizontal surface with adequate load bearing capacity.
>>
Base frames must be levelled horizontally (check with a spirit level).
•
To prevent the inspection doors from jamming, the entire base frame must sit on the foundation.
Point loads are not permitted!
>>
Provide permanently elastic noise insulation in the form of insulation strips between the installation
surface and the base frame. (This provides insulation against structure-born noise.)
Fig. 6.2 Insulation against structure-borne noise for the building
1
Insulation against structure-borne noise
3
Insulation if required
2
Roof membrane
>>
The Solid Air base frame must be insulated and integrated into the roof membrane onsite.
>>
In the case of elevated positioning (CPL on onsite framework), the CPL must be secured against wind load.
Fig. 6.3 Insulation against structure-borne noise for the frame
1
Insulation against structure-borne noise