NOTE
Electrical voltage!
Damage to components of the appliance.
>>
Never route sensor leads alongside 230 V or 400 V cables.
>>
Power connection lines must be in line with the specifications for the appliance and the local conditions.
>>
Only use cables that meet local wiring regulations with regard to voltage, current, insulation material, load etc.
>>
Provide earth conductor.
>>
Integrate the appliance properly into the onsite lightning protection system.
>>
Connect the unit to the onsite equipotential bonding system.
>>
Check the earth conductor and insulation resistance in accordance with EN 60204 (VDE 0113) while taking all
necessary safety precautions.
I We accept no liability for any damage or loss resulting from technical modifications to Solid Air control units.
I If control voltage is present or a set speed is saved, the EC fans will restart automatically after power failure.
6.8.2 Power cable cross-section/onsite fuse protection
6.8.3 Motor data
CPL
1400
2400
3300
4700
6100
Rated voltage
1 x 230 V (50/60 Hz) 3 x 400 V (50/60 Hz) 3 x 400 V (50/60 Hz) 3 x 400 V (50/60 Hz) 3 x 400 V (50/60 Hz)
Maximum power consumption/maximum
current draw of both fans
1,0 kW/
4,6 A
2,1 kW/
3,2 A
4,8 kW/
7,2 A
5,0 kW/
8,0 A
5,0 kW/
8,0 A
Speed
3080 1/rpm
3400 1/rpm
3700 1/rpm
3100 1/rpm
2500 1/rpm
IP rating/protection class
IP55/Iso F
IP55/Iso F
IP55/Iso F
IP55/Iso F
IP55/Iso F
CPL
Power cable
Onsite fuse/MCB
CPL-1400
3 x 1,5 mm²
16 A
CPL-2400
5 x 1,5 mm²
16 A
CPL-2400 with electric coil
5 x 2,5 mm²
20 A
CPL-3300
5 x 1,5 mm²
16 A
CPL-3300 with electric coil
5 x 4,0 mm²
25 A
CPL-4700
5 x 2,5 mm²
20 A
CPL-6100
5 x 2,5 mm²
20 A