The wall is composed of concrete blocks (minimum density of 550 kg/m³) or reinforced
concrete (minimum density of 2200 kg/m³) and with a minimum thickness of 100 mm.
1
2
3
RIGID WALL
INSTALLATION
MF1/MF2 INSTALLATION FRAME
INSTALLATION
1. Create an opening in the wall (FDC25- Ø d +10 mm, FDC40-Ø d + 25 mm).
Damper blade must be closed during installation!
2. Place the damper in the opening.
3. Fasten the fire damper with screws.
FDC25: 4 pcs 6 x 160 mm
FDC40: 12 pcs 6 x 160 mm
Test the operation of the damper blade!
>
>