52-400-2G-1-PAO
S
OLID
S
TATE
C
OOLING
S
YSTEMS
,
167
M
YERS
C
ORNERS
R
OAD
,
W
APPINGERS
F
ALLS
,
NY
12590
7
T
ELEPHONE
:
(845)
296-1300
F
AX
:
(845)
296-1303
WEB
V
ERSION
M9
S
ECTION
3
H
OOK
UP ________________________________________________________________
3.1
E
LECTRICAL
C
ONNECTIONS
Power: Plug line cord into 115/230 VAC, +/- 10%, 50/60 Hz,
continuous current draw is rated at 7amps (100 VAC) or 5 amps
(230VAC)
at 50/60 Hz.
Fuse: 10 amp (5mm x 20mm) GDB quick acting glass, meets
IEC 127-2
Replacement Fuse: SSCS#20-22332-10, Allied Electronics
#740-9575
Alarms: The ThermoCube has two normally closed 1 amp 250V dry
contact alarm relays instead of the standard TTL alarms, one for
system faults and one for temperature exceeding the alarm range.
These contacts are wired to the 9-pin dsub connector as follows:
System Fault Alarm Common:
Pin 6
System Fault Alarm:
Pin 1
Temperature Alarm Common:
Pin 9
Temperature Alarm:
Pin 4
3.2
P
LUMBING
C
ONNECTIONS
The process fluid inlet (coolant return) and outlet (coolant supply)
connections, located on the left side, are ¼” Colder Products metal
quick disconnect fittings (female), model number LCD16004V. Note:
Viton o-rings must be specified.
3.3
A
IR
C
ONSIDERATIONS
The air inlet and outlet are located on the left and right sides
respectively. Restricting airflow into or out of the unit will impair
performance. At least 3 inches of clearance is required on each side to
ensure adequate airflow.
3.4
C
OOLANT
F
ILL
C
AP
The coolant fill cap is located at the top rear of the unit. Twist off the
cap counter-clockwise to open. Fill reservoir prior to starting unit.
Close cap before operating.