GETSET2 parameters
: GETSET2 returns the following data w/o identifying prefix names.
Note: All data returned is in ASCII
•
Cr defined at “carriage return” or 0D
hex
•
ETX defined as “end-of-text” or 03
hex
Data
Description
Format
Units
Range
TEMP<Cr>
Coolant Temperature
XX.X
°C
5.0 – 45.0
SETTEMP<Cr>
Set Point Temperature
XX.X
°C
5.0 – 45.0
PUMPTEMP<Cr>
Pump Temperature
XX.X
°C
0.0 – 50.0
PWM<Cr>
%PWM
XX.X
%
0 – 98.0
FANPWM<Cr>
%PWM
XX.X
%
40-100
TLL<Cr>
Tank Lev Low
XXXX
none
0 - 4096
STAT1A<Cr>
Status bits
XXXXX
none
0 - 65535
FLTS1A<Cr>
Fault bits
XXXXX
none
0 - 65535
<ETX>
ASCII “end of text”, 03
hex
03
n/a
03
Example: Running, remote mode, ready, coolant temp 22.9°C, set-point 23.0°C, pump temp 17.0°C, 76.3%
cooling, Fan Speed 69.2%, tank level low = 119, status: running in remote mode within alarm range, faults: none
22.9<Cr>23.0<Cr>17.0<Cr>-76.3<Cr>69.2<Cr>119<Cr>7<Cr>0<Cr><ETX>
STAT1A
Bit Field Definition: convert decimal number sent into binary, read as follows:
|__ __ __ __ | __ __ __ __ | __ __ __ __ | __ __ __ __ |
| | | | | | | | | | | | | | | |___Chiller Running?
1 = RUNNING, 0 = STOPPED
| | | | | | | | | | | | | | |_____Remote or Local
1 = REMOTE, 0 = LOCAL
| | | | | | | | | | | | | |________Chiller Ready?
1 = READY, 0 = NOTREADY
| | | | | | | | | | | | |__________Temp low alarm
1 = Temp < SP - WIDTH
| | | | | | | | | | | |______________Temp high alarm
1 = Temp > SP + WIDTH
| | | | | | | | | | |_____________Chiller Heating or Cooling 1 = HEATING, 0 = COOLING
| | | | | | | | | |__________________System Warning
1 = WARNING, 0 = NONE
| | | | | | | | |_____________________System Alarm
1 = ALARM, 0 = NONE
|_______ rsvd ____| |__________________________ rsvd
The Warning bit is triggered by tank level low and a temperature outside of the +/- alarm width.
The Alarm bit is triggered by an RTD fault, a pump fault, or a fan fault.
FLTS1A
Bit Field Definition (Fault=”1”) convert decimal number sent into binary, read as follows:
|__ __ __ __ | __ __ __ __ | __ __ __ __ | __ __ __ __ |
| | | | | | | | | | | | | | | |___ RTD
| | | | | | | | | | | | | | |_____ Tank Level Low
| | | | | | | | | | | | | |________ Pump Fail
| | | | | | | | | | | | |__________ Fan Fail
| | | | | | | | | | | |______________ rsvd
| | | | | | | | | | |_________________ rsvd
| | | | | | | | | |___________________ rsvd
| | | | | | | | |______________________ rsvd
| | | | | | | |__________________________ rsvd
| | | | | | |____________________________ rsvd
| | | | | |_______________________________ rsvd
| | | | |_________________________________ rsvd
|_ rsvd_|