4.
MAINTENANCE
Table 1 below details the maintenance schedule necessary to ensure optimal continued operation of the
BlueGEN appliance. The appliance will detect and schedule its maintenance requirements automatically. The
information provided below indicates the average maintenance requirements for a typical installation.
The control system of the BlueGEN appliance ensures that automated alerts are sent to SP support personnel
to notify of an impending maintenance task, or if a component requires maintenance outside the normal
maintenance schedule.
There are no user-serviceable parts and so end-users should have no need to open the BlueGEN appliance
cabinet doors for inspections or replacements.
Table 1: Recommended maintenance schedule for BlueGEN appliance
Caution
Under no circumstances should the end-user open the BlueGEN appliance cabinet doors.
Serviceable
Components
Inspection
Replacement Interval
Time Required (approx.)
Desulphuriser
Canister
N/A
1-3 years
1
1 hr
Air Filter
N/A
12 months
1
15 min
CO/CH4 sensor
N/A
2 years
30 min
Water Treatment
System
1 hr (total)
RO filters
N/A
3 years
1
Demineralisation
filter
N/A
12 months
1
Demineralisation
filter (polishing)
N/A
2 years
1
Carbon filter
N/A
12 months
1
Sediment filter
N/A
12 months
1
Condensate
Recovery System
30 min
Condensate Resin
filter
N/A
12 months
1
1.
Depends on site water/gas/air quality.