Heat Pump For Heating And Cooling Series
5. Installation
5.1 Heat Pump unit Installation
1. The heat pump unit should be installed in a
be as three times of weight as the heat pump unit.
ventilated place, with enough space for air inlet
Reliable measures should be taken to keep the
and outlet, while without thermal radiation or
fastener stable. The unit base should be fixed
other heat source. Besides, the air outlet should
firmly by expansion bolts to ensure the entire unit
not be against the wind.
stand erectly after installation.
2. Generally, the vertical air flow type heat pump
10. The unit location should avoid typhoon and
does not need anything for sheltering. The motor
earthquake damage. The heat pump should not
and other internal components have been all
be installed in the air in case of crash accident.
waterproof. A shelter is required to avoid snow
11. The installation should be carried out
burying onto the heat pump in heavily snowy
at the place of unobstructed ventilation of
area.
the air outlet. (The inlet and outlet of the
3. Please make sure the rated voltage 380V or
air blower are illustrated in the following
400V is stably accessible to the heat pump,
diagram). The installation space should be
otherwise the performance would be influenced.
referred as follows:
4.The foundation of the heat pump can be cement
or steel structure. Anti-vibration rubber and a flat
foundation should be taken into account. The
foundation structure can be flexibly designed
according to the working weight of the heat
pump(Please see the technical data in this
manual.)
5. Water drainage should be available near the
installation location for draining water in an
effective way.
6.Do not install the heat pump in a place where
there is polluting or corrosive material like oil,
flammable and explosive gas and sulfide etc.
Keep it far away from sands, falling leaves and
area with high-frequency equipment.
7.The foundation should be heightened to avoid
the water inflow in rainy season and snow burying
in winter if it is installed in the open air.
8. Installation in balcony or on roof-top must be
accordance with the allowable stress of the
building structure.
9.The heat pump should be fixed firmly on the
base. The bearing capability of the frame should
Up
flow
more than
2000mm
more than
1000mm
more than
1000mm
air inlet
air inlet
Horizontal View
enough space for
maintenance
more than
1000mm
more than
1000mm
more than
1000mm
air inlet
air inlet
air inlet
Vertical View
7