5. Operation
.42.
NOTE:
5G products support lead-acid battery. Select "Lead-
A
cid" in the
" Battery Select" and configure the following parameters according
to different lead-acid batteries.
Lead
A
cid Battery
201 5-02-23 1 9 35
Battery Capacity:
1 00
A
h
Equalizing Voltage:
56.4V
Floating Voltage:
53.5V
Overdischg Voltage:
44.5V
Floating Current:
04.0
A
Force Charg Voltage:
43.BV
I_Max Discharge:
060.0V
Temp.Compensation:
072mV/degC
I_Max Charge:
01 0.0
A
S E T = < E N T > D O N E = < E S C >
Lead
A
cid Battery (Values are examples Only)
1. Battery Capacity: Define the capacity of the battery.
2. Equalizing Voltage: Define the voltage for equalizing charge.
3. Floating Voltage: Define the voltage for floating charge.
4. Floating Current: Define the current for floating charge.
5. Overdischg Voltage: Define the voltage that stops discharging the battery.
6. Force Charg Voltage: Define the voltage that forces to charge the battery
to prevent a dead battery.
7. I_Max Discharge: Define the max discharge current for the battery.
8. I_Max Charge: Define the max charge current for the battery.
9. Temp.Compensation: Define the temperature compensation parameter
for the battery.
A
fter configuration, save and send. Select the Environment Temp based on
real condition.(Hot/Warm/Cold)
5. Operation
Lead
A
cid Battery
201 5-02-23 1 9 35
E nv i ro n m e n t Te m p :
Y E S = < E N T > N O = < E S C >
WARNING:
Lead-acid battery is not recommended for general customers as it requires
experienced installers and technicians who can fully understand the battery
parameters and configure the settings and installations correctly.
Due to the inconformity between battery cells, damages will be less likely to be
avoided. Solis is not responsible for any potential damages caused by the use
of lead-acid batteries.
.43.