4. Installation

5. Operation

Monthly Energy

Main interface

information

settings

advanced info.

advanced settings

UP/DOWN

UP/DOWN

UP/DOWN

Pressing the ENTER 

key to switch 

to the submenu

Pressing the ESC 

key calls back 

the previous menu

main menu

Figure 5.1 Operation Overview

ESC

ESC

ENTER

Description

The inverter can detect DC power.

No DC power.

The inverter is fully operational.

The inverter has stopped operating.

The inverter is initializing.

Fault condition is detected.

No fault condition detected.

Status

ON

OFF

ON

OFF

OFF

ON

FLASHING

Light

POWER

OPERATION

ALARM

4.11 LED Indicates

There are three LED indicators on the RHI inverter (Red, Green, and

 

Orange) which indicate the 

working status of the inverter.

Table 4.1 Status Indicator Lights

FLASHING

Either the grid or solar cannot be detected.

5.1 Initial Display

When powering up the inverter for the first time, it is required to set the language. 

Press "ENT" to select.

Figure 5.2 Set Language

Settings

Set

 

Language

2015-02-23   19 35

English

中文

Y E S

=

< E N T >

   

N O

=

< E S C >

.22.

.23.

Summary of Contents for RHI-3.6K-48ES-5G

Page 1: ...Industrial Park Xiangshan Ningbo Zhejiang 315712 P R China Tel 86 0 574 6578 1806 Fax 86 0 574 6578 1606 If you encounter any problem on the inverter please find out the inverter S N and contact us we...

Page 2: ...5 Assembling the AC Connector 4 6 Meter Installation 4 7 Communication Cable Assembly 5 Operation 5 1 Initial Display 5 3 Information 5 4 Settings 4 2 3 Notice For Use 6 3 3 Terminal Connection 21 4...

Page 3: ...1 Introduction 1 2 Packaging Please ensure that the following items are included in the packaging with your machine If anything is missing please contact your local Solis distributor RJ45 connector x...

Page 4: ...AUTION Risk of electric shock from energy stored in capacitors of the Inverter do not remove cover for 5 minutes after disconnecting all power sources service technician only Warranty may be voided if...

Page 5: ...2 The electrical installation must meet all the applicable regulations and standards 3 The inverter must be installed according to the instructions stated in this manual 4 The inverter must be install...

Page 6: ...ept between inverters or objects and 500mm clearance between the bottom of the machine and the ground Visibility of the LEDs and LCD should be considered Adequate ventilation must be provided NOTE Not...

Page 7: ...4 5 Wall Mount Bracket WARNING The inverter must be mounted vertically 2 Lift up the inverter be careful to avoid body strain and align the back bracket on the inverter with the convex section of the...

Page 8: ...the terminal protection cover as indicated in Figure 4 7 Figure 4 7 Installation of Terminal Protection Cover Note Before connecting the battery please carefully read the user manual of the battery an...

Page 9: ...re you use a cable within the correct speci cations as shown in the image below 3 Remove a length of 40mm of the cable jacket and strip the wire insulation to a length of 8 15mm 2 Lead the AC cable th...

Page 10: ...bes the connection diagram of the Acrel 1ph meter With CT Standard Accessory for all other market exclude Italy Below 4 6 2 section describes the connection diagram of the Eastron 1ph meter Direct Ins...

Page 11: ...formation please contact the sales manager For lead acid battery battery SOC calculation may not be accurate according to battery inconformity between cells battery aging or other specifications of le...

Page 12: ...g to the standard line sequence of figure 4 13 connect the wire to the plug of RJ45 and then use a network cable crimping tool to make it tight Correspondence between the cables and the stitches of pl...

Page 13: ...ating The inverter is initializing Fault condition is detected No fault condition detected Status ON OFF ON OFF OFF ON FLASHING Light POWER OPERATION ALARM 4 11 LED Indicates There are three LED indic...

Page 14: ...Fail Critical Loads Loads connected to the AC Backup port which will be supported by battery and solar even if the grid is in malfunction Grid The arrow and value indicate the export import power of t...

Page 15: ...26 27 Figure 5 8 Information Page 4 Settings Information 2015 02 23 19 35 4 4 Grid Meter Meter Voltage Meter Current Meter Power Meter Energy Input Energy 000 0V 00 00A 000000W 0000 00kWh ESC UP DOWN...

Page 16: ...daily yield calculation If Solis monitoring system is used must set the correct time zone of the system otherwise datalogger will update the inverter time based on the time zone of the system Press UP...

Page 17: ...16 Model Version and Software Version Battery Enable Disable 5 5 Advanced Information Detailed information can be viewed in this section 1 Alarm Message 2 Running Message 3 Version 4 Communication Dat...

Page 18: ...ly Energy Figure 5 18 Daily Energy Daily Energy 2015 02 23 19 35 2015 23 02 00 10 20 30 40 50 60 D a i l y E n e r g y k W 00 00 03 00 06 00 09 00 12 00 15 00 18 00 21 00 00 00 ESC UP DOWN ENT The scr...

Page 19: ...F Settings Warning Message 2015 02 23 19 35 Message Date Time Data NO message ESC UP DOWN ENT 5 5 9 Warning Message Figure 5 22 Warning Message Settings 5 5 8 Total Energy The screen shows the inverte...

Page 20: ...Energy Adjusting total generating power 2015 02 23 19 35 Total Energy ESC UP DOWN ENT Y E S E N T N O E S C Total Energy 00000 kWh 56 This function is used to select corresponding grid standards Pleas...

Page 21: ...wer 2015 02 23 19 35 Power Para ESC UP DOWN ENT Y E S E N T N O E S C Power Parameter 1 000 5 6 4 Reset Password Reset Password In this page user can reset the inverter password but the admin password...

Page 22: ...y going into sleep mode when the ForceCharge SOC is reached inverter will charge the battery using the power from either PV or Grid NOTE If hybrid inverter is not connected to a battery select No Batt...

Page 23: ...oating Current I_Max Discharge I_Max Charge Equalizing Voltage Force Charg Voltage 100Ah 53 5V 04 0V 010 0A ESC UP DOWN ENT 060 0V Overdischg Voltage 56 4A 44 5A 43 8V S ET E N T D ONE E S C Lead Acid...

Page 24: ...Optional Eastron 3ph meter Direct Insert SDM630M Optional Eastron 3ph meter With CT SDM630MCT Optional No meter is connected 5 6 6 3 2 Meter Placement Grid Meter is installed at the grid connection p...

Page 25: ...g polarity the inverter can protect itself from damage To avoid the possible damage during installation do not active battery wakeup function before nishing the rst commissioning 5 6 6 5 Battery Wakeu...

Page 26: ...S C U P D AT E S Y S T E M E N T Figure 5 50 BaudRate RS485 Settings BaudRate RS485 2015 02 23 19 35 Y E S E N T N O E S C Baud Rate 9600 ESC UP DOWN ENT 5 6 10 BaudRate RS485 This function is to chan...

Page 27: ...tivity otherwise it will lead to frequent false alarms or malfunctions Manufacturer is not responsible for any further damages caused by unauthorized modifications NOTE If you find your inverters s us...

Page 28: ...witch between inverter and battery 4 Waiting for the LCD of inverter to turn off and the system shutdown is completed 1 Switch on the AC backup and AC grid 2 Select grid standard 3 Con gure the parame...

Page 29: ...tion 2015 02 23 19 35 Warning Message Version Daily Energy Monthly Energy Yearly Energy Total Energy Running Message Communication Data Alarm Message KWH 2 526 0 00kW 0 00kW 0 00kW 0 00kW The inverter...

Page 30: ...essage G IMP NO GRID OV BUS GRID INTF01 02 INI FAULT Failure description High grid impedance No grid voltage Over DC bus voltage Grid interference Initialization system fault Solution 1 Check connecti...

Page 31: ...river connection UN G V01 02 12Power FAULT 12V power supply fault 1 Restart inverter or contact installer Table 8 1 Fault message and description 8 Troubleshooting Max input voltage Start up voltage M...

Page 32: ...t AC Grid side Power Factor Max efficiency EU efficiency 0 99 0 8 leading 0 8 lagging 96 8 Max output current 15 7A 17 3A THDi 2 Efficiency Protection Ground fault monitoring Residual current mornitor...

Page 33: ...V Max short circuit current 17 2A 17 2A Battery Output AC Back up Input AC Grid side Input voltage range Frequency range 184 264V 26 1A 45 55 Hz 55 65Hz Max input current 20ms Rated output power 5kW 4...

Page 34: ...ncy range 184 264V 26 1A 45 55 Hz 55 65Hz Max input current 20ms Li ion Lead acid 100A 5kW Features Quick connection plug AC connection Communication Warranty RS485 Optional Wi Fi GPRS 5 years standar...

Page 35: ...available in Belgium Features Quick connection plug AC connection Communication Warranty RS485 Optional Wi Fi GPRS 5 years standard extand to 20 years Display 7 0 LCD color screen display Grid connec...

Page 36: ...inverter Make sure the polarities of battery is correct before connecting to the inverter Please follow the instructions below to choose the battery power cable NOTE Power cable uses water proofed AMP...

Page 37: ...y item 1 rstly Then assemble back shell item 4 onto the connector body item 1 and tighten No gap When 16mm cable apply assembly barrelinto lug rstly as shown Then put the conductor into the lug Tie cl...

Page 38: ...PV Battery Grid Battery Charging Power comes from PV If Charging From Grid is allowed it can also come from Grid If Time of Use is Run the logic will follow the charging discharging settings and time...

Page 39: ...attery Load Support Priority PV Battery Grid Battery Charging Power comes from PV If Charging From Grid is allowed it can also come from Grid If Time of Use is Run the logic will follow the charging d...

Page 40: ...nexpected control mistakes EPS Mode Path Advanced Settings Storage Energy Set Storage Mode Select EPS Mode EPS En Disable Enable Settings EPS Mode 2015 02 23 19 35 S ET E N T D OWN E S C Mode 4 Off Gr...

Page 41: ...and Netherland France Belgium South Africa Italy UK UK North Ireland North Ireland Comments For German Low Voltage Grid For Polish Low Voltage Grid For Dutch Low Voltage Grid General EN50438 Requireme...

Reviews: