background image

 

Green Power Function

Ultima UPS is equipped with green power function.  For saving power and protecting 

battery, this method of deep discharging protection is adopted on inverter mode.

Free power monitoring software on CD

•  Choose the operation system you need and follow the instructions described on the  

  CD to install the software.

Note

: If you find the communication unsuccessful after monitoring software installation, 

you have to switch the Auto Search on and you can only do that if you go into 'Act as 

Administrator'. Once selected, the software will hunt for and find the UPS.

Note

: The power switch must be kept in the ‘ON’ position, otherwise, the UPS will be 

disabled and your equipment will not be protected during a power failure.

Note

: If you change your UPS model, please ensure you uninstall and reinstall the Software.

  Troubleshooting guide:

©Sollatek (UK) Limited 1996 All Rights Reserved. SOLLATEK and the SOLLATEK device are the trade marks of the Sollatek group of companies.

Sollatek (UK) Ltd. 
Unit 10, Poyle 14 Industrial Estate, Newlands Drive, Horton Road, Poyle, Slough, Berkshire SL3 0DX, UK

Tel:   +44 (0) 1753 688300   

Fax:  +44 (0) 1753 685306   

   

Technical support: support@sollatek.com

Sales: sales@sollatek.com   

www.sollatek.com  

Rev. no. 1.0 April 07. 

 Problem  

Possible Cause  

Solution

 No LED display on the front panel. 

1. Battery weak. 

1. Re-charge battery up to 8 hours.

  

2. Battery defect. 

2. Replace with the same type of battery.

  

3. Power switch is not pressed. 

3. Press the power switch again.

  

 

 

Alarm buzzer beeps continuously when AC supply is normal. 

UPS overload. 

Verify that the load matches the UPS capability specified in the  

  

 

specs.

  

 

When power failure, back-up time is shortened. 

1. Overload of the UPS. 

1. Remove some noncritical load.

  

2. Battery voltage is too low. 

2. Charge battery 8 hours or more.

  

3. Battery defect due to high temperature  

  

operation environment, or improper  

  

operation to battery. 

3. Replace with the same type of battery.

Communication lost between UPS and computer 

1. Software is not properly installed. 

1. Check the setting of the software. 

 

  

2. Interface cable is not properly connected. 

2. Check the interface cable is properly connected to the COM1/COM2 of  

  

 

the computer and confirm the setting again.

  

 

Mains normal bottom but UPS is not working. 

1. Fuse is blown. 

1. Replace with the same type of fuse.

  

2. Power cord is loose. 

2. Reconnect the power cord properly.

Proper care of batteries

•   Do not subject the battery to heavy vibration or mechanical shock.
•   When you receive a new battery, charge fully before use.
•   Full capacity will be reached after 2 or 3 full charge/discharge cycles.
•   To obtain maximum life, always store batteries in a charged state.
•   When storing batteries, re-charge every 6 months to prevent damage through self 

discharge. This should be done more often if storage temperature exceeds 25ºC.

•   Try to store / use in a cool, dry place. Do not expose to excessive hot 

or cold (i.e. outside the range 10-35°C ambient temp).

•   To prolong battery life, try to avoid the complete discharge 

of your battery before recovery charge.

•   Do not discharge a battery deeper than you have to.
•   Do not attempt to dismantle a battery. They do not require topping up.

•   Do not incinerate batteries. Always recycle old batteries.

•   To avoid the risk of shock, do not touch the terminals.

•   Keep terminals free from dirt and corrosion.

•   Do not short the connections. 

•   Always charge in a ventilated area.

•   Always use a suitable charging device. If unsure, contact your distributor.

•   Replace only with Sollatek recommended replacement batteries.  

If unsure, contact your distributor.

MODEL 

 

Ultima 400 

Ultima 600 

Ultima 800 

CAPACITY  

VA/W 

400VA/240W 

600VA/360W 

800VA/480W

INPUT 

Voltage 

 

120VAC or 220/230/240VAC

 

Voltage range 

 

85-140VAC or 162-290VAC

 

Frequency  

 

45-65 Hz (auto sensing)

OUTPUT 

Voltage 

 

120/220/230/240VAC

 

Voltage regulation  

 

(batt. mode) 

 

+/-10%

 

Frequency 

 

50Hz or 60Hz

 

Frequency regulation  

 

(batt. mode) 

 

+/-1 Hz

 

Output waveform 

 

modified sinewave

BATTERY 

Battery type 

12V 4.5Ah x 1  

12V7Ah x 1 

12V9Ah x 1

 

Recharge time 

  8 hours to 90% after complete discharge

TRANSFER TIME 

Typical 

 

2-6 ms

INDICATOR 

AC mode 

 

green lighting

 

Backup mode 

 

green flashing

AUDIBLE ALARM 

Backup mode 

 

sounding every 10 seconds

 

Low battery 

 

sounding every second

 

Overload 

 

sounding every 0.5 second

 

Battery replacement 

 

sounding every 2 seconds

 

Fault 

 

continuously sounding

PROTECTION 

Full protection 

 discharge, overcharge, and overload protection

PHYSICAL 

Dimension (mm),  

 

D x W x H 

 

330 x 100 x 140

WEIGHT 

Net weight 

5kgs 

6kgs 

6.5kgs

ENVIRONMENT 

Operating  

 

environment 

 

0- 40°C, 0-90 % relative humidity  

 

 

 

(non-condensing)

 

Noise level 

 

Less than 40dB

INTERFACE 

RS-232      Windows, Sun Solaris, IBM Aix, Compaq True64, UnixWare, FreeBSD, HP-UX, Linux, MAC 

USB 

 

 

Windows 98/2000/ME/XP

 

  Specifications

 

   

CHARGE THE UPS AT LEAST 8 HOURS BEFORE USE, ENSURING  

   

THE BATTERY LEVEL INDICATOR IS FULL

Battery replacement

WARNING: Disconnect all sources of supply before replacing battery. 

1. TURN UPS UNIT UPSIDE 

DOWN
Locate 4 screws on underside 

of UPS unit, and remove. 

2. RETURN UPS UNIT TO ITS CORRECT POSITION. 
The top half of the casework will now lift off.

The front fascia will now hinge down, revealing battery. 

Gently pull out the battery. Disconnect the two wires 

that are connected to the UPS. To reassemble the fascia , 

ensure the 2 lugs are located correctly.

Replacement battery installation is the reversal of this 

procedure.

Ensure the wires on the battery are connected back 

exactly the way they were connected originally. 

Caution! UPS may get damaged if these wires are 

connected incorrectly - if in doubt, contact Sollatek.

•   Replace only with Sollatek recommended replacement batteries.  

If unsure, contact your distributor.

2 lugs

          

          
          

Ultima battery back-up times 

(in minutes)

 

 

200VA 

300VA 

400VA 

600VA 

800VA 

1000VA  1200VA 

1400VA  1600VA  1800VA

Ultima 400 

<3 

<1 

Ultima 600 

15 

<5 

<1

Ultima 800 

22 

12 

<3 

<1

TM

t h e   p o w e r   t o   p r o t e c t