All-in-one solar charge inverter 24
Parameter
no.
Parameter
name
Settings
Description
06
Charger source
priority
[06] CSO
PV priority charging; only when the PV
charging fails, the mains charging is started.
[06] CUB
Mains priority charging; only when the mains
charging fails, the PV charging is started.
[06] SNU
default
PV and Mains hybrid charging; PV charging is a
priority, and when the PV energy is insufficient,
the Mains charging supplements. When the PV
energy is sufficient, the Mains charging stops.
Note: Only when the Mains bypass output is
loaded, the PV charging and the mains
charging can work at the same time. When the
inverter works, only the PV charging can be
started.
[06] OSO
Only PV charging, with the Mains charging not
activated.
07
Max charger
current
[07] 80A
default
Max charger current (AC PV charger).
Setting range: 0~140A;
08
Battery Type
[08] USE
User-defined; all battery parameters can be set.
[08] SLd
Sealed lead-acid battery; constant-voltage
charge voltage: 28.8V, floating charge voltage:
27.6V.
[08] FLd
Vented lead-acid battery; constant-voltage
charge voltage: 29.2V, floating charge voltage:
27.6V.
[08] GEL
default
Colloidal lead-acid battery; constant-voltage
charge voltage: 28.4V, floating charge voltage:
27.6V.
[08]
LF07/LF08/LF09
Lithium iron phosphate battery LF07/LF08/LF09,
corresponding to 7 strings ,8 strings and 9
strings of lithium iron phosphate battery; for 7
strings, default constant-voltage charge voltage
is 24.8V; for 8 strings, default constant-voltage
charge voltage is 28.4V; for 9 strings, default
constant-voltage charge voltage is 31.8V; allow
adjustable.