P32-EN – Subject to technical changes 04.11
26
8.4 Menu overview (technician level)
Main menu:
1 2 3 4 5 6 7 8 9 10 11 12 13 14
MENU
Version
User
Date/Time
Meas.Val.Overview
Function Overview
Inputs
Outputs
Functions
Messages
Potentiostat
Data Administration
User menu*:
1 2 3 4 5 6 7 8 9 10 11 12 13 14
USER
OPERATING MODE:
Client
Technician
✓
Expert
DISPLAY:
Contrast: 40
Reset menu*:
1 2 3 4 5 6 7 8 9 10 11 12 13 14
DATA ADMINISTRATION
Current Funct. Data:
SD-11205.dat
Status: original
Load Factory Setting
Create Backup Copy
Load Backup copy
WW Requirements menu:
1 2 3 4 5 6 7 8 9 10 11 12 13 14
WW REQUIREMENT
WARM WATER TEMP.:
T.WW.ACT: 48°C
T.WW.NOM: 48°C
TIME PROG:
T.WW.MIN: 0°C
DIFF.ON: 9.0
K
DIFF.OFF: 12
K
Burner perf.:
100%
Circulation menu*:
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CIRCULATION
DES.: CIRCU
OPERAT.: Time
CIRCU. RETURN:
T.CR.ACT: 48°C
T.CR.NOM: 48°C
TIME PROG:
DIFF.ON: -12
K
DIFF.OFF: -9.0
K
WARM WATER TEMP.:
T.WW.ACT: 48°C
Version display:
1 2 3 4 5 6 7 8 9
1
0 11 12 13 14
SOLVIS
SolvisControl
Operat.Syst: A2.08EN
Boot Sector: B2.07
Function overview:*
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Operat.Syst: A2.08EN
HEAT CIR.1
F:17
OPERAT.: TIME/AUTO
Normal
TIME PROG:
T.Pre.ACT: 8.5°C
T.Pre.NOM: 48.5°C
HEAT CURVE:
WW_REQ.1 F:10
REQUIREMENT:
Status: OFF
T.WW.NOM: 48°C
TIME PROG:
———————————
CIRCU
F:16
OPERAT.: Time
TIME PROG:
HELP
SERVICE
* Sections displayed
Heating circuit control menu*:
1 2 3 4 5 6 7 8 9 10 11 12 13 14
HEAT CIRC.CONT
DES.: HEAT CIR.1
OPERAT.: TIME/AUTO
Normal
ROOM TEMPERATURE:
T.Room.ACT: ------°C
T.Room.LOWER: 16°C
T.Room.NORMAL: 20°C
TIME PROG:
Rate time:
0 min
T.Room.EFF: 20.0°C
PRE-RUN TEMPERATURE:
T.Pre.ACT: 35.7°C
T.Pre.NOM: 35.2°C
HEAT CURVE:
OUTDOOR TEMPERATURE:
T.Out.ACT: 13°C
AVG. TIME:
SWITCH-OFF COND.:
FROST PROTECTION:
Average menu:
1 2 3 4 5 6 7 8 9 10 11 12 13 14
AVG TIME VALUES
HEAT CIR.1
For Pre-run Control:
AVG-Time: 10
min
T.OutAVGcon: 13°C
For Switch-Off:
AVG-Time: 30
min
T.OutAVGoff: 12 °C
Switch-off cond. menu:
1 2 3 4 5 6 7 8 9 10 11 12 13 14
SWITCH-OFF COND.
HEAT CIR.1
if T.room
ACT> NOM ? no
Hysteresis: 1.0 K
if T.Pre.
NOM < MIN ? yes
Hysteresis: 2.0 K
if T.out
AVGoff > MAX ? yes
T.Out.MAX: 19°C
Hysteresis: 2.0 K
if lowering operat.
and T.out
ACT > MIN ? yes
T.Out.MIN: 10°C
Hysteresis: 2.0 K
if Heating Circ. OFF
MIXER: close
Frost protection menu:
1 2 3 4 5 6 7 8 9 10 11 12 13 14
FROST PROTECTION
Activation if
T.OutAVGcon <
3°C
T.Room.FROST: 5°C