P32-EN – Subject to technical changes 04.11
30
Setting the controller and start-up
8.7 Setting the impulse rate (optional)
If you have installed a volume flow measuring unit for
measuring the solar yield, be sure that the correct quantity
per impulse is set on the controller.
The volume flow measuring unit from Solvis (item no.:
09499, order separately) has a quantity of 0.5 l per
impulse (factory setting at controller).
If you are using on-site volume flow measuring units,
you have to set the quantity per impulse at input 15 of
the SolvisControl.
You can only make the setting in the “Technician” oper-
ating mode. To do this, proceed as follows:
In the function overview, press the “SERVICE” button. In
the main menu, select the “Inputs” entry by turning and
pressing the rotary wheel. In the Outputs menu, position
the pointer on “PAR?” beneath the entry “15: Flow.Sol.2”
and press the rotary wheel. Turn the rotary wheel in the
menu that opens up until the pointer is on “QUOTIENT:
0.5 l/Imp” (
figure on right
). Set the value you require by
pressing and turning the rotary wheel until the required
value appears and then pressing it again. Press the
“BACK” button several times to return to the function
overview.
1 2 3 4 5 6 7 8 9 10 11 12 13 14
BROWSE
BACK
DES: Solar Flow2
QUOTIENT:
0.5 l/Imp
MEAN(An):
1.0 sec
INPUT 15
At the pointer position
set the quantity per
impulse
In the function overview, press the “SERVICE” button. In
the main menu, select the “Outputs” entry by turning and
pressing the rotary wheel. In the Outputs menu, position
the pointer on “AUTO/OFF” beneath the entry “7: Solar
Pump2” and press the rotary wheel. Turn the rotary wheel
until “HAND/ON” appears, and then press it. The pump
is now in operation, and the number “7” in the top row
is highlighted black (
figure on right
). Press the “BACK”
button several times to return to the function overview.
1 2 3 4 5 6
8 9 10 11 12 13 14
OUTPUTS
BROWSE
BACK
6: Solar Pump1
HAND/ON
PAR?
HAND/OFF
PAR?
RPM stage:
0
7: Solar Pump2
7
8.6 Function check of outputs (pumps)
If you want to switch on a pump manually – such as for a
function check – proceed as follows (example using pump
in secondary solar circuit):
Outputs 6 and 7 (solar pumps) are set to manual
mode. Output 6 to “HAND/OFF”, output 7 to
“HAND/ON” (note that 7 is highlighted in black
in the row of numbers above)