P32-EN – Subject to technical changes 04.11
54
Additional Information for Installers
Menu, plain text
Factory
setting
1 2 3 4 5 6 7 8 9 10 11 12 13 14
SOLAR CONTROL
DES.: SOLAR 1
FUNCTION STATUS:
INPUT VARIABLE:
OUTPUT VARIABLE:
COLLECTOR TEMPERATURE:
T.Coll.ACT: 30°C
T.Coll.MAX: 120°C
Hysteresis: 20 K
REFERENCE TEMPERATURE:
T.Ref.ACT: 24°C
T.Ref.MAX: 90°C
90
Hysteresis: 3.0 K
3
DIFFERENCE COLL-REF:
DIFF.ON: 15 K
15
DIFF.OFF: 10 K
12
LIMIT TEMPERATURE:
T.Lim.ACT: 58°C
T.Lim.MAX: 95°C
95
Hysteresis: 3.0 K
Open
: In the Functions menu, function “2: SOLAR
CONTROL”
Description
: This function controls the solar circuit of your
solar system. The factory settings guarantee you the best
possible utilization of the available sunlight.
The “T.Coll.ACT” line shows the temperature of the col-
lector at the hottest point. At “DIFF.ON” and “DIFF.OFF”,
you can read the switch-on and switch-off temperature
differences, respectively.
The temperature at the S3 storage tank reference sensor
(see system diagram in the appendix) can be read at
“T.Ref.ACT” and the temperature at the hot water buffer
temperature sensor (S1) can be read at “T.Lim.ACT”.
Solar control menu overview
10.3.2 Solar control function “SOLAR 1”
1 2 3 4 5 6 7 8 9 10 11 12 13 14
SOLAR CONTROL
BROWSE
BACK
DIFFERENCE COLL-REF:
DIFF.ON:
15 K
DIFF.OFF:
10 K
At the pointer position
, read or set the collector
switch-off temperature difference
Press the “SERVICE” button in the function overview to
go to the main menu. In the main menu, select the
“Functions” menu item and press the rotary wheel. In the
Functions overview menu, select the menu item function
“PAR?” of function “2: SOLAR CONTROL” and press the
rotary wheel. Turn the rotary wheel until “DIFF. OFF: 10 K”
is selected with the pointer (see
figure right
). Now you can
change the value by pressing, turning and pressing the
rotary wheel. Press “BACK” several times to return to the
function overview.
Possible settings:
For example
Setting the switch-off difference
:
The controller must be in the “Technician” operating mode
(
page 25
). Proceed as follows:
You should only change the switch-on and switch-
off differences in exceptional cases.