P32-EN – Subject to technical changes 04.11
64
Appendix: Information on SolvisControl system controller
11.1.4 Technical data
Electrical connection
Mains voltage
230 V/50-60 Hz
Microfuse
6.3 A/230 V fast-acting
Ambient temperature
0 to 45°C
Power consumption
Approx. 5 W (in slumber mode, without pumps)
Timer function without power supply
Approx. 1-2 days
Sensors and display
Temperature sensor type
PTC 2 kOhm (all sensors except S5 and S6: PT 1000)
Temperature display
-50 to +199°C
Display resolution
0.1 K
Measurement accuracy
Typically 0.4 and max. ± 1°C in 0 to 100°C range
Sensor and function check
Display “9999”
Sensor not connected, sensor (cable) breakage
Display “999”
Sensor (cable) short circuit
Inputs and sensor positions
S1: Temperature sensor
Upper buffer (on cable harness, included in delivery)
S2: Temperature sensor
Hot water sensor (included in delivery)
S3: Temperature sensor
Storage tank reference (on cable harness, included in delivery)
S4: Temperature sensor
Upper heating buffer (on cable harness, included in delivery)
S5: Temperature sensor
Solar flow, secondary (cable harness FKB-SÜS)
S6: Temperature sensor
Solar return, secondary (cable harness FKB-SÜS)
S7: Temperature sensor
Solar flow, primary (cable harness FKB-SÜS)
S8: Temperature sensor
Collector temperature (FKY 5,5)
S9: Temperature sensor
Lower heating buffer (on cable harness, included in delivery)
S10: Temperature sensor
Outdoor temperature (optional)
S11: Temperature sensor
Temperature of circulation return (optional)
S12: Temperature sensor
Heating flow, heating circuit 1 (optional)
S13: Temperature sensor
Heating flow, heating circuit 2 (optional)
S14: Temperature sensor
Return temperature hot water heat exchanger
S15: Volume flow measuring unit (impulse input)
Volume flow in secondary solar cycle (optional)
S16: Temperature sensor
Room sensor, alternative: Swimming pool water temperature
Outputs
A1: Primary swimming pool pump and contactor (parallel)
Switch output 230 V/max. 0.7 A
A2: Hot water production pump
(1)
Speed controller, wave packet, 230 V, max. 1.7 A
A3: Heating circuit pump, heating circuit 1 (optional)
Switch output 230 V/max. 3 A
A4: Heating circuit pump, heating circuit 2 (optional)
Switch output 230 V/max. 3 A
A5: Circulation pump (optional)
Switch output 230 V/max. 3 A
A6: Solar circuit pump, primary (optional)
(1)
Speed controller, wave packet, 230 V, max. 1.7 A
A7: Solar circuit pump, secondary (optional)
(1)
Speed controller, wave packet, 230 V, max. 1.7 A
A8: Heating circuit mixer, heating circuit 1 open
Switch output 230 V/max. 3 A
A9: Heating circuit mixer, heating circuit 1 closed
Switch output 230 V/max. 3 A
A10: Heating circuit mixer, heating circuit 2 open
Switch output 230 V/max. 3 A
A11: Heating circuit mixer, heating circuit 2 closed
Switch output 230 V/max. 3 A
A12: Heating requirement, burner
Switch output 230 V/max. 3 A
A13: Charging pump
Switch output 230 V/max. 3 A
A14: Data transfer
Switch output floating max. 230 V / 3 A
A15: Analogue output
Modulation 0 to 10 V for gas or oil boiler (
page 25
)
Interfaces
DL
Connection for data line, 2-wire
CAN BUS
Connection for data line, 4-wire
Infrared IR
Data transfer to the controller front (e.g. bootloader)
(1)
No electronically controlled pumps (e.g. WILO E series, Grundfos UPE, etc.) or pumps with 3-phase motors may
be connected to the speed-controlled outputs.