10
a) b)
Figure 5 – Minimum separation distance around the unit: a) top view of the unit installation; b) side
view of the unit installation
WARNING!
Keep combustible and flammable materials at a safe distance.
5.2. Installing Ducts and Fume Extraction Systems:
The exhaust pipe must be designed for this specific purpose, in compliance with
local requirements and any applicable regulations.
Important notice! An inspection-T with an airtight lid must be attached to the
outlet of the unit’s exhaust pipe to allow for the regular inspection of the system or
discharge of heavy dust and condensates.
As illustrated in figure 5, the exhaustion path must have inspection slots along the
duct to facilitate the performance of periodic cleaning and maintenance operations.
Under normal operating conditions, the combustion gas flow should create a
draught of 12 Pa, measured one meter above the chimney neck.
This unit requires exclusive use of the chimney.