background image

 

 

 

Summary of Contents for 1870398

Page 1: ......

Page 2: ...ited for mainte nance and repair work e g glued or extensively glued floors installation behind lamps or panels any additional costs incurred as a result shall not be borne by the seller Subject to technical modifications The Motor Controller 6 AC KNX DRM is suitable for controlling up to six individually configurable motors for Venetian blinds roller shutters awnings and windows Functions and adv...

Page 3: ...lousie 90 90 Winkel 0 Wendung 50 KNX Bytewert 127 Jalousie 90 90 Winkel 90 Wendung 0 KNX Bytewert 0 255 maximal geschlossen maximal gewendet Jalousie 90 90 maximal gewendet Jalousie 90 0 Wenderichtung Wenderichtung Wenderichtung nach AB Fahrt Position 100 KNX Bytewert 255 maximum closed maximum reversed Venetian blind 90 0 maximum reversed Venetian blind 90 90 Venetian blind 90 90 Angle 0 Tilt 50 ...

Page 4: ...Motor Controller 6 AC KNX DRM 30 11 2020 Ref 5157011A 4 26 2 Installation DIN rail version of Motor Controller 6 AC KNX DRM Wire and switch power supply on Switch cabinet 10 cm ...

Page 5: ...NX Reset Prog SCR US EU M Motor Controller 6AC KNX DRM 1870398 220 230 V 10 A µ Prog D Connected to Cable Twisted pairs Stripping length Motors Min 4 x 0 75 mm 18 AWG Max 4 x 2 5 mm 13 AWG 6 mm KNX bus 2 x 0 5 mm2 20 AWG Mandatory in accordance with KNX topology instruc tions 6 mm 220 230 V AC Min 3 x 1 5 mm 15 AWG Max 3 x 2 5 mm 13 AWG 6 mm ...

Page 6: ... hold the Reset Prog button Switch the power on again and keep the Reset Prog button depressed for 10 seconds until 2 LEDs flash 3 times The motor controller is now reset to the factory settings 4 1 2 Resetting to factory settings via ETS The reset is indicated after approx 15 seconds by the LEDs on the device lighting up briefly 4 1 3 Motor controller status check Press the Reset Prog button brie...

Page 7: ...Furthermore if a telegram with the value 1 is received the slats close and if a tel egram with the value 0 is received they move up wards The turn duration is determined in the pa rameter settings For vertical awnings roller shutters awnings and windows If a telegram is received by one of these communi cation objects when one of the end devices is mov ing the movement is stopped regardless of whet...

Page 8: ... the value re ceived 0 upper end limit 100 lower end limit For Venetian blinds When the position is reached the slats are turned to the same position as they were in before 26 Motor 2 Position Up Down manual 1 Byte 5 001 27 Motor 3 Position Up Down manual 1 Byte 5 001 28 Motor 4 Position Up Down manual 1 Byte 5 001 29 Motor 5 Position Up Down manual 1 Byte 5 001 30 Motor 6 Position Up Down manual ...

Page 9: ... is received by one of these communication objects the current posi tion of the corresponding blind is saved as interme diate position 1 If a telegram with the value 0 is received by one of these communication objects intermediate posi tion 1 is deleted 50 Motor 2 IP 1 Save Delete 1 Bit 1 002 51 Motor 3 IP 1 Save Delete 1 Bit 1 002 52 Motor 4 IP 1 Save Delete 1 Bit 1 002 53 Motor 5 IP 1 Save Delet...

Page 10: ...tions configured in the ETS software for the corresponding blind are no longer blocked and are released again 68 Motor 2 block functions 1 Bit 1 001 69 Motor 3 block functions 1 Bit 1 001 70 Motor 4 block functions 1 Bit 1 001 71 Motor 5 block functions 1 Bit 1 001 72 Motor 6 block functions 1 Bit 1 001 73 Motor 1 Prio automatic manual 1 Bit 1 001 With these communication objects priority can be s...

Page 11: ...otor 6 position feedback 1 Byte 5 001 97 Motor 1 Feedback Slat 1 Byte 5 001 With these communication objects the actual posi tion of the slats is sent to the bus based on the pro grammed tilting time This type of message on re quest in the event of a position change or cyclical is configured in the ETS parameters Depending on the parameter settings on the General index card the position is defined...

Page 12: ...object when the lower end limit is reached If the lower end limit of the corresponding blind is left a telegram with the value 0 is sent The upper and lower end lim its are determined by means of the configured travel times 110 Motor 2 Feedback Lower End 1 Bit 1 002 111 Motor 3 Feedback Lower End 1 Bit 1 002 112 Motor 4 Feedback Lower End 1 Bit 1 002 113 Motor 5 Feedback Lower End 1 Bit 1 002 114 ...

Page 13: ...the motor outputs are configured in a combined or individual process If the Combined parameter is selected only one menu index card is visible for the basic settings of all six motor outputs motor 1 6 The Combined option is recommended for projects where the configuration of the motor outputs is the same If the Individual parameter is selected six menu index cards are visible for configuration of ...

Page 14: ...transmitted to the corresponding object 19 24 31 36 the slats are reversed or com pletely open 6 1 4 Automatic cascading reduces power spikes through motors Default value No Selection options No Yes If this parameter is set to Yes the motor outputs move to the corresponding position with a 1 second delay This delay is taken into account when starting the positions which are generated based on the ...

Page 15: ...d via the object motor 1 6 tilting step stop Screen roller shutter awning This parameter determines that the corresponding vertical awning roller shutter or awning can be controlled via the relevant object motor 1 6 up down and via the object motor 1 6 stop Window This parameter determines that the corresponding window can be controlled via the relevant object motor 1 6 close open and via the obje...

Page 16: ...ponds to the length of a tilting step This parameter is only visible if Type of end product is set to Venetian blind 6 2 6 Slack compensation Default value 0 seconds Selection options 0 5 seconds The mechanical compensation time is active as soon as a value greater than 0 is input The time set here corresponds to the total time added to the tilting time to take account of mechanical tolerances Thi...

Page 17: ...d upwards again 6 3 Functions motor 1 6 menu index card If the Individual basic setting for the motors is selected on the General menu index card six individual menu index cards functions of motors 1 6 are visible If the Combined basic setting for the motors is se lected on the General menu index card one menu index card functions of motors 1 6 is visible 6 3 1 Intermediate Position 1 IP 1 6 3 1 1...

Page 18: ...configured travel times of the corresponding blind on the menu index card Motor 1 6 Motor 1 6 If the Up Down intermediate position is set to 0 the function is disabled 6 3 2 2 IP 2 Slat position 0 100 Default value 0 Selection options 0 100 This parameter sets the intermediate position 2 Slat The target value in refers to the configured com plete slat tilts of the corresponding blind on the menu i...

Page 19: ...ed by one of these communication objects no operation is per formed If the Restore previous position after security function is set to Yes on the Functions motor 1 6 menu index card it will be checked regardless of whether the low priority is active or inactive If low priority value 1 is active the blinds move to the Security position low priority position see previous point If low priority value ...

Page 20: ... command 1 bit or byte is received before an automatic command 1 byte all automatic com mands and IP 2 will be disabled Priority for manual functions is reset if Reset priority receives 1 or 0 at the corresponding object 79 84 The switch between priority for manual functions value 0 and priority for automatic functions value 1 is performed via the corresponding objects 73 78 After switching to the...

Page 21: ...y then will further Up Down orders bit be blocked If a telegram with value 0 is received by the corre sponding object the Up Down orders bit will be allowed again 6 4 2 Block automatic tilting orders Default value No Selection options No Yes This parameter allows tilting orders byte to be blocked via the object 67 72 If a telegram with value 1 is received by the corresponding object while the blin...

Page 22: ...th value 1 is received by the corresponding object while the blind is moving this operation will be completed Only then will further Up Down orders bit be blocked If a telegram with value 0 is received by the corre sponding object the Up Down orders bit will be allowed again 6 4 5 Reaction at main power return 230 V for all motors Default value Ignore Selection options Upper end limit Lower end li...

Page 23: ... for the corresponding motor is sent to the bus according to the Type of feedback parameter 0 Upper end limit 100 Lower end limit Slat position With this parameter the position of the slats for the corresponding motor is sent to the bus according to the Type of feedback 0 slats open 100 slats closed The value for the slats position communicated via the corresponding object depends on the parameter...

Page 24: ...on options 1 second 5 seconds 10 seconds 20 seconds 30 seconds 1 minute 5 minutes 10 minutes 20 minutes 30 minutes 60 minutes This parameter determines the time intervals at which the current position of the corresponding blinds is communicated The current position of the corresponding blinds is communicated to the bus ...

Page 25: ...per motor output 3 A cos φ 0 95 Max total current for all motor outputs 10 A cos φ 0 95 External overcurrent protection 16 A fuse required Relays Microgap μ Terminals Spring connectors KNX connection terminals KNX connection terminals black red Duration per output Max 5 minutes Operating temperature 5 C to 50 C Relative humidity Max 85 non condensing at 30 C Material of housing PC ABS Housing dime...

Page 26: ...Motor Controller 6 AC KNX DRM 30 11 2020 Ref 5157011A 26 26 ...