Environment
Storage
enenvironment
Indoor use only, temperature: 0~50
℃
no condensation,
humidity
<
85%RH, altitude<2000m
-10
~
60
℃
, no condensation
1. Electrical parameters:
IV. Specifications
Sample rate
2 times per second
Relay capacity
AC 250V /3A Life of rated load>100,000 times
SSR output
DC 24V pulse voltage, load<30mA
Communication port
Current output
Insulation impedance
ESD
Pulse traip
anti-interference
DC 4
~
20mA load<500Ω, temperature drift 250PPM
RS485 port Modbus-RTU protocol, max input 30 units
Input, output, power VS meter cover
>
20MΩ
IEC/EN61000-4-2 Contact ±4KV /Air ±8KV perf.Criteria B
IEC/EN61000-4-4 ±2KV perf.Criteria B
Power supply
Power consumption
AC/DC 100
~
240V
(
85-265V
)
< 10VA
Intelligent Temperature Controller
User Manual
Applicable TFY
-A version
1
⊙
Optional input signal types and models
⊙
With functions of measurement display, control output, alarm output, analog
output, RS485 communication, etc.
⊙
Multi PID control algorithms for option, and with auto-tune function.
⊙
This product is used in industrial machinery, machine tools, general measuring
instruments and equipment.
Features
The instruction explain instrument settings, connections,name and etc, please read
carefully before you use the temperature controller. Please keep it properly for necessary
reference.
TFY4
□
-
□
R C 1 8
□
-A
II. Ordering information
1
2
3
A: Version
10: Single input without RS485
18: Single input with RS485
Blank: TC/RTD/mV/Rt input
X: mA/V input
4
5
B: 1 alarm output C: 2 alarm output
R: Relay output S: SSR output
D: DC 4~20mA output (can be changed to analog
output by ACT menu) K: SCR output (can be
ordered) M: SSR or relay (switched by ACT)
6
Blank: No this function.
I: DC 4~20mA analog
output (can be switched to control output by
ACT menu, available for TE6 & TE9)
7
8
9
4: 48H*48W*73L 6: 96H*48W*73L 7: 72H*72W*73L
8: 48H*96 W*73L 9: 96H*96W*73L
TFY series temperature controller
Blank: AC/DC 100
~
240V
F: AC/DC 24V
2
Analog
output
Comm.
Auxiliary
power
RELA
Y
SSR 4
~
20mA AL1
O
UT
2
AL2 4
~
20mA RS485 24V
TFY4-DC18
□
●
● ●
◎
●
●
TFY4-DC10
□
●
● ●
◎
◎
●
TFY4-RC18
□
●
● ●
●
●
TFY4-SC18
□
●
● ●
TFY4-MC10
□
●
●
● ●
TFY7-DC18
□
●
●
●
●
◎
●
●
TFY7-DC10
□
●
● ●
TFY7-MC18
□
●
●
●
●
●
●
TFY7-MC10
□
●
● ●
TFY6/8/9-IMC18
□
●
●
●
● ●
◎
●
●
●
◎
●
●
◎
●
●
●
TFY6/8/9-IMC10
□
●
● ●
TFY6/8/9-DC18
□
● ●
●
●
●
◎
●
●
TFY6/8/9-DC10
□
●
TFY6/8/9-MC18
□
● ●
● ●
●
TFY6/8/9-MC10
□
● ●
● ●
O
UT
1 control output Alarm output
Model
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
●
III. Models
□
:
Blank: input signal is TC/RTD/Mv/Rt; “X” : input signal is 4
~
20mA/0
~
10V
●
:
Standard configuration function
◎
:
The meter has this function, but it is combined with another function. This series only have
one loop 4~20mA output, but the user can modify menu ACT to use it as main control output or
analog output.
I. Safe Caution
Warning
Caution
1
)
When the failure or abnormal of products lead to a system of major accidents, please set
the proper protection circuit in the external.
2
)
Please don`t plug in before completing all the wire.Otherwise it may lead to electric shock,
fire, fault.
3
)
Not allow to use outside the scope of product specification,otherwise it may lead to
fire,fault.
4
)
Not allow to use in the place where is inflammable and explosive gas.
5
)
Do not touch power terminal and other high voltage part when the power on, otherwise
you may get an electric-shock.
6
)
Do not remove,repair and modify this product,otherwise it may lead to electric shock, fire,
fault.
1
)
The product should not be used in a nuclear facility and human life associated medical
equipment.
2
)
The product may occur radio interference when it used at home.You should take
adequate countermeasures.
3
)
The product get an electric shock protection through reinforced Insulation. When the
product is embedded in the devices and wiring,please subject to the specification of
embedded devices.
4
)
In order to prevent surge occurs,when using this product in the place of over 30m indoor
wiring and wiring in outdoor, you need to set the proper surge suppression circuitry.
5
)
The product is produced based on mounting on the disk.In order to avoid to touch the
wire connectors,please take the necessary measures on the product.
6
)
Be sure to observe the precautions in this manual, otherwise there is a risk of a major
injury or accident.
7
)
When wiring, please observe the local regulation.
8
)
To prevent to damage the machine and prevent to machine failure, the product is
connected with power lines or large capacity input and output lines and other methods
please install proper capacity fuse or other methods of protection circuit.
9
)
Please don't put metal and wire clastic mixed with this product,otherwise it may lead to
electric shock, fire, fault.
10
)
Please tighten screw torque according to the rules.If not,it may lead to electric shock and
fire.
11
)
In order not to interfere with this products to dissipate heat, please don't plug casing
around the cooling vent hole and equipment.
12
)
Please don’ t connect any unused terminal.
13
)
Please do the cleaning after power off, and use the dry cleaning cloth to wipe away the
dirt. Please don’ t use desiccant, otherwise, it may casue the deformation or discoloration
of the product.
14
)
Please don`t knock or rub the panel with rigid thing.
15
)
The readers of this manual should have basic knowledge of electrical,control, computer
and communications.
16
)
The illustration, example of data and screen in this manual is convenient to
understand,instead of guaranteeing the result of the operation.
17
)
In order to use this product with safety for long-term,regular maintenance is necessary.
The life of some parts of the equipments are by some restrictions, but the performance of
some will change for using many years.
18
)
Without prior notice, the contents of this manual will be change. We hope these is no
any loopholes, if you have questions or objections, please contact us.
Caution of Install & Connection
1. Installation
1) This product is used in the following environmental standards.
(
IEC61010-1
)
[Overvoltage
category
Ⅱ、
class of pollution 2]
2)This product is used in the following scope:environment, temperature, humidity and
environmental conditions.Temperature:0~50
℃
;humidity: 45~85%RH; Environment
condition:Indoor warranty.The altitude is less than 2000m.
3) Please avoid using in the following places
:
The place will be dew for changing temperature;with corrosive gases and flammable gas;with
vibration and impact;with water, oil, chemicals, smoke and steam facilities with Dust, salt,
metal powder;and with clutter interference, static electric and magnetic fields, noise;where
has air conditioning or heating of air blowing directly to the site; where will be illuminated
directly by sunlight; where accumulation of heat will happen caused by radiation.
4) On the occasion of the installation, please consider the following before installation.
In order to protect heat saturated, please ensure adequate ventilation space.
Please consider connections and environment,and ensure that the products below for more
than 50mm space. Please avoid to installed over the machine of the calorific value (Such as
heaters, transformer, semiconductor operations, the bulk resistance). When the surrounding
is more than 50 , please using the force fan or cooling fans.But don't let cold air blowing
directly to the product. In order to improve the anti - interference performance and security,
please try to stay away from high pressure machines, power machines to install.
Don`t install on the same plate with high pressure machine and the product.
The distance should be more than 200mm between the product and power line.
2. Cable caution
:
1
)
Please use specified compensation wire in the place of TC input; Please use insulated TC
if the measured device is heated metal.
2
)
Please use the cable of lesser resistance in the place of RTD input,and the cable(3 wire)
must be no resistance difference,but the total length is within 5m.
3
)
In order to avoid the effect of noise,please put the input dignal away from meter
cable,power cable,load cable to wiring.
4
)
In order to reduce the power cables and the load power cables on the effect of this
product,please use noise filter in the place where easy to effect.
You must install it on the grounding of the disk if you use the noise filter,and make the wiring
to be shortest between noise filter output side and power connectors. Don`t install fuse and
switch on the wiring of noice filter output side,otherwise it will reduce the effect of noise filter.
5
)
It takes 5s from input power to output.If there is a place with interlocking actions circuit
signal,please use timer relay.
6
)
Please use twisted pair with a shield for analog output line, can also connect the
common-mode coil to the front-end of the signal receiving device to suppress line
interference if necessary, to ensure the reliabilty of signal.
7)Please use twisted pair with a shield for remote RS485 communication cable, and deal with
the shield on the host side earth, to ensure the reliabilty of signal.
8
)
This product don’ t have the fuse; please set according to rated voltage 250V,rated current
1A if you need; fuse type:relay fuse.
9
)
Please use suitable slotted screwdriver and wire.
Terminal distance: 5.0mm. Screwdriver size: 0.6X3.5, length of slotted screwdriver >130mm.
Recommended tightening torque: 0.5N.m.
Proper cables: 0.25
~
1.65mm single cable/multiple core cable
10
)
Please don`t put the Crimp terminal or bare wire part contact with adjacent
connector.