background image

Symbol description: “

” means HY, “▲” means alarm value, “    ” means SV value

7

8

9

10

11

12

SV

SV

SV

SV

SV

SV

SV-AL1

SV-AL1

SV-AL1

SV+AL2

SV+AL2

SV+AL2

AL2

AL2

AL2

AL1

AL1

AL1

1

2

4

5

6

SV+AL

SV+AL

SV-AL

SV-AL

SV

SV

SV+AL

SV-AL

AL

SV

SV

SV

SV

PV

PV

PV

PV

PV

PV

PV

PV

PV

PV

PV

PV

AL

SV

SV

SV

SV

SV

SV

SV-AL1

SV-AL1

SV-AL1

SV+AL2

SV+AL2

SV+AL2

AL2

AL2

AL2

AL1

AL1

AL1

2

3

SV+AL

SV+AL

SV-AL

SV-AL

SV

SV

SV+AL

SV-AL

AL

SV

SV

SV

SV

PV

PV

PV

PV

PV

PV

PV

PV

PV

PV

PV

PV

AL

(1) Alarm parameters and output logic diagram:

Alarm 

code

Alarm mode

Alarm output

AL1 & AL2 are independent from each

Image:the hatched section means the alarm action

High limit absolute value 

alarm

Low limit absolute value 

alarm

High limit deviation

value alarm

Low limit deviation value 

alarm

High/low limit deviation 

value alarm

High/low limit interval 

value alarm

Alarm 

code

Alarm mode

The below two alarm parameters(AL1,AL2) are used in

combination, AL1 alarm output, AD2 must be set as 0

High and low limit absolute 

value interval alarm

High and low limit deviation 

value interval alarm

High limit absolute value 

and low limit deviation value

interval alarm

High limit deviation value 

and low limit absolute value

interval alarm

High/low limit absolute value 

alarm
High/low limit deviation value 

alarm

 For deviation alarm, if alarm value is set as a negative number, it will be used as an absolute 

value.

No.

 Name

Symbol

Illustration

Setting range

Factory

setting

1

2

4

AL1

HY1

AD1

 

1

AL2

HY2

AD2

 

1

FL

FH

0

1000

0

12

FL

FH

0

1000

0

6

-1999

9999

10

1

3

5
1
4

0

6

5

OT

0

5

INP

K1

1

0

9999

120

1

200

20

4

200

20

PC

10.0

OVS

0

9999

5

DB

-1000~1000

5

LCK

0~9999

0

0

9999

30

8

9

0

9999

30

A-M

AUTO~AM

AUTO

10

3

AD1

 

1

PS

0

12

3

7

I

CP

CP1

0.1

100.0

OVS

LCK

P

12

13

14

15

16

17

18

19

11

D

1st alarm hystersis

2nd alarm value, 
2nd alarm hystersis  
2nd alarm mode 

OUT1  control cycle, 1: SSR control output,

4-200: relay control output. Unit: s
OUT2 relay output cycle. Unit: s
OUT2 cooling proportionality coefficient, the higher of 

value,the stronger of cooling

ON/OFF control hystersis(positive and negative 

numbers work the same); when OT=3, it is the dead 

zone for cooling control(positive and negative 

numbers work differently);after change the INP 

setting, please change this parameter according to 

the decimal point position.

Lock function. 0001:SV value can’ t be modified. 

0010: menu set value can be checked only, can’ t

be modified. 0033: enter to advanced menu. 

0123: menus reset to factory setting.

Overshoot limit, during PID control process, when 

PV(measured value) > SV(set value) + OVS

(overshoot limit), force to close output. The smaller 

this value is, the smaller the PID adjustment range 

is, the worse the control stability is. Please set the 

appropriate value according to the actual situation.

Differential time, the greater the value is, the stronger 

the differential actiontion is, otherwise, it is weeker. 

When D=0, no differential action. Set D=0 when 

controlling fast systems, e.g., pressure, speed; unit: s

Integral time, the smaller the value is, the stronger the 

integral action is, otherwise, it is weeker. When I=0, 

no integral action, unit: s.

Proportional band, the smaller the value is, the faster 

the system responds, otherwise, it is slower. When 

P=0, no PID control, unit same as PV

Amend value, display value= actual measured value 

+ amend value

Control mode, 0:ON/OFF heating control, relevant 

parameter: DB.

1: PID heating control, relavant parameters:

P, I, D, OVS, CP, ST, SPD, PDC.

2: ON/OFF cooling control, relevant parameter DB; 

need to set PT when it is used for compressor control.

3:PID heating & cooling control (cooling control OUT2 

will output through AL1 relay), relevant parameters: P, 

I, D, OVS, CP, CP1, PC, DB, ST, SPD, PDC.

4: Over temperature cooling output

 relevant

parameter: DB

5. PID cooling, relevant parameter: P, I, D, OVS, CP, 

ST, SPD, PDC.

Optional input signal. Note: after selecting the signal, 

pls properly set below relevant parameters: SV, AL1

 

HY1

 AL2

 HY2

 P

 OVS

 DB.

Auto-manual control switch, AUTO(0): auto control 

only; MAN(1): manual control only; 

AM(2): auto-manual shortcut switch

refer to input 

signal para-

meters table

(page 3)

1st alarm mode. Note:when AL1 is used as OUT2(co-

oling output), should set AD1=0(close alarm function). 

When AD1>6, 2nd alarm function is invalid.

No.

 Name

Symbol

Illustration

Setting range

Factory

setting

IX. Menu Illustration

1. Regular Menu

No mater what model, what control mode it is, it will always display these parameters.

According to different model, control mode, these parameters will be hidden. 

1st alarm value, note: the minus is dealed as absolute 

value when it is set as deviation alarm. Refer to 

(1) Alarm parameters and output logic diagram

 

5

6

2

Operation examples

1. Set target

temperature

SV=100

2

Advanced Menu

22

20

21

ACT

Control execution type. 0: relay or SSR output.

1:SSR output (Code type M select this item). 

2: 4~20mA control output, 3: 4~20mA retransimition 

output for size 4/7 products. Note:For size 6/8/9 

products, when this menu is set as 0 or 1, 4-20mA 

output is used as retransimition output.  

0~2

6/8/9 size

0~3

4/7 size

0

AE1

1st alarm extensions function, refer to (2) alarm 

extension function table

0~5

0

0~5

0

0~3

0

AE2

DP

2nd alarm extensions function, refer to (2) alarm 

extension function table
Decimal point setting, maximum 1 decimal place for 

TC & RTD input

23

2. Set menu

INP=K

3. Set menu

OT=0

4. Set menu

DB=2

5. Set menu

ACT=0

6. Set menu

AL1=110

7. Set menu

HY1=5

8. Set menu

AD1=1

1. Set target

temperature

SV=150

2. Set menu

INP=pt

3. Set menu

OT=1

4. Set menu

OVS=5

5. Set menu

ACT=0

6. Set menu

AL1=5

7. Set menu

HY1=7

8. Set menu

AD1=3

25

150

inp

pt

ot

1

5

ACT

0

AL1

5

HY1

7

AD1

3

1

Example 1, ON/OFF control

     Sensor

K type, measure range -50~1300

; target temperature: 100

; control mode: 

heatin; control requirement: ON/OFF control, when current temperature PV reaches 100

stop heating; when PV is lower than 98

, start heating again; control output: relay; alarm: 1 

alarm, when PV>110

, alarm output on; when PV<105

, alarm output off. 

2

Example 2, PID control: 

     Sensor: PT100, measure range -200~600

; target temperature: 150

; control mode: 

heating; control requirement: PID control (note: in order to get stable temperature control, 

please use the auto-tuning function when the controller is powered on for the first time; if the 

temperature control is stable after the auto tuning, there is no need to repeat this step in the 

future usage.); control output: SSR; alarm: 1 alarm, when PV>SV+5

, alarm output on, 

when PV<SV-2

, alarm output off. 

25

100

inp

ot

0

db

2

ACT

0

AL1

110

HY1

5

AD1

1

42

43

45

CAL

CAH

VER

YES/OK

YES/OK

YES

YES

44

SSM

~

 1

0

Software version, read only

Self-calibration low limit input operation, after adding 

the low end signal to the signal input terminal, flash 

YES to activate, after confirm and display OK, the 

input signal low end calibration is completed.
Self-calibration high limit input operation, after adding 

the high end signal to the signal input terminal, flash 

YES to activate, after confirm and display OK, the 

input signal high end calibration is completed.
Enable R/S key to switch RUN / STOP operation. 

0: Forbidden   1: Enable    This setting is only for

panel operation, not for communication operation.

CAE

0

N

1

Y

N

41

User self-calibration enable function, this parameter 

is only for the input signals except TC/RTD; 

Y:enable the self-calibration parameters;

N: don’ t use the self-calibration parameters.

No.

 Name

Symbol

Illustration

Setting range

Factory

setting

27

28

FL

-50

FH

1200

29

30

31

32

33

34

35

BRH

OLH

ST

SPD

0.0

105.0

0~1

0~1

1200

100.0

BRL

FL~FH

FL~FH

OLL

0

0

0~6

N

PDC

FUZ

-5.0~100.0

-50 

36

PT

0~9999

0

37
38

BAD

ADD

DTC

9.6

1

1~247

0

Modbus Communication ADD

39

40

0~2

0~2

N0

PRTY

PV fuzzy tracking value, properly set this value on 

some occasions, it can get a more stable control 

display value, this value is unrelated with actual 

measured value. Note: after setting this value, when 

alarm setting value is equal to SV set value, alarm 

output operation is subject to actual measured value. 

Set as 0 to close this function.

26

Filter coefficient, the higher of value, the stronger of 

filter function

UT Temperature unit: 

: Celsius degrees. 

: Fahrenheit 

degrees.  Note: No unit for linear signal

(25)

(25)

(26)

25

FT

0

255

10

(0~20)

DTR

0.0

2.0

(10)

1.0

24

0

0~2

Measuring range low limit and high limit. 

For temperature sensor input, please keep the factory 

setting value. For 4 ~ 20mA / 0 ~ 10V input, please 

set the corresponding range for the low limit and the 

high limit. For example, 0~10V corresponds to -20~50, 

set FL to - 20, set FH to 50. Setting range: 

-1999~9999, associated with DP decimal point menu.

4~20mA analog output low limit and high limit. For

example, 4~20mA  corresponds to 0~100, set brL to 0, 

set brH to 100. Note: it can be set as reverse analog

output, for example, 100~0 corresponds to 4~20mA.

Current control output low limit and high limit, only 

valid for 4~20mA current control output. It is used to 

limit the output current amplitude. For example, in the 

control of frequency converter, if the motor cannot be 

stopped,  please set the output low limit OLL to 10%; 

in heating control, if the user don’ t want full-power 

output at the beginning of heating, please set the 

output high limit OLH to 80%.

Compressor start delay time, unit: sec

Baud rate 0 (4.8): 4800

 1 (9.6): 9600;

2 (19.2): 19200

Communication parity check setting

0

NO 1

ODD 2

EVEN

Communication data transport sequence 000;

1st bit function reserved; 2nd bit is byte sequence 

exchange; 3rd bit function reserved.

Auto-tune activation after power-on, 0: work normally 

after power-on, 1: automatically enter PID parameters 

auto-tune status after power-on; long press “ AT ”  key 

to exit auto-tune.
PID control speed adjustment,option: 0 (N) no function,

 

1 (s) slow, 2 (ss) medium slow, 3 (SSS) very slow, 

4 (F) fast, 5 (FF) medium fast, 6 (FFF) very fast
PID algorithm option:   0(FUZ): Advanced fuzzy PID 

arithmetic;     1(STD): normal PID arithmetic

Refer to

measured 

signal

parameter table

Refer to

measured 

signal

parameter table

Refer to COMM.

protocol 

note

Reviews: